44(86) | Cabling and connections |
6.2.2.1Digital input signal inversions
The active signal level depends on which potential the common inputs CMA and CMB (terminals 11 and 17) are connected to. The alternatives are either +24V or ground (0 V). See Figure
The
+24V
Ground
DIN1
DIN2
DIN3
DIN1
DIN2
DIN3
Ground
CMA
+24V
CMA
Positive logic (+24V is the active signal) = the input is active when the switch is closed
Negative logic (0V is the active signal) = the input is active when the switch is closed
Figure 6-18. Positive/Negative logic
6.2.2.2Jumper selections on the NXOPTA1 basic board
The user is able to customise the functions of the frequency converter to better suit his needs by selecting certain positions for the jumpers on the NXOPTA1 board. The positions of the jumpers determine the signal type of analogue and digital inputs.
On the A1 basic board, there are four jumper blocks X1, X2, X3 and X6 each containing eight pins and two jumpers. The selectable positions of the jumpers are shown in Figure
Figure 6-19. Jumper blocks on NXOPTA1
6