2.5 Communication Ports

Pulsar MX RT provides 4 communication methods.

1.The RS232 port provides communications using MGE UPS SYSTEMS Serial HID UPS transfer (SHUT) protocol. The SHUT protocol is compatible with the power management applications available on the enclosed Solution-Pac 2 CD-Rom.

2.The Output contacts port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.

3.The USB port is compatible with the power management applications available on the enclosed Solution-Pac 2 CD-Rom.

4.The slot is compatible with the optional 66102 — Network Management Card (NMC) 2006 Edition and the 66103-Status Card.

Note All communications options can be used simultaneously except for the SHUT RS232 and USB port. If both the USB and SHUT ports are connected then the USB takes control.

Connection to the RS232 or USB communication port (42)

1 Connect the RS232 (42) or USB (44) communi- cation cable to the serial or USB port on the computer equipment.

2. Connect the other end of the RS232 cable (42) to the RS232 (7) communication port or the USB cable (not included) to the USB port (6) on the UPS.

The UPS can now communicate with various MGE UPS SYSTEMS power management application software.

Please note that Personal Solution-Pac can be used to configure (personalize) the UPS parameters such as voltage, frequency, battery test, etc. See section 4.6 for more details.

Connection to the communication port by relays (8)

8

Pin 1, 2: not used,

Pin 3: Remote Power Off signal (5 to 27 V DC, 10 m A max),

Pin 4: Operation on mains (not on battery),

Pin 5: User common,

Pin 6: Operation on automatic by-pass,

Pin 7: Low battery,

Pin 8: Load protected,

Pin 9: Operation on battery.

n.o: contact normally open.

n.c: contact normally closed.

When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.

Output relays specifications:

Voltage: 48 V DC max,

Current: 2 A max,

Power: 62.5 VA, 30 W.

Example: for 48 V DC, Imax=625 mA

86-87050-00 A01

Installation

2 — 5

Image 19
Contents Pulsar MX Page Pulsar MX Pulsar MX Contents Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesEnvironmental protection IntroductionImportant Safety Instructions Symbol Usage This page left blank intentionally 86-87050-00 A01 Rack Position PresentationStandard Positions Tower PositionPulsar MX 5000 RT Pulsar MX EXB RT Transformer Rear PanelsDisplay and Control Panel Accessories for Rack MountRack Mounting Kit Battery extensions for Pulsar MX RT Extended Battery EXBBattery Integration System Kit with Casters Optional battery extension cable 6 ft/1.8 mUnpacking and Contents Check Installation Installation in Tower Position Internal Battery Connection Battery Start-upTo adjust the display position Installation in Rack PositionRear bracket system included with rail kits Connection to the RS232 or USB communication port Communication PortsConnection to the communication port by relays Recommended upstream protection Remote Power Off communication portInstallation of optional Communication card Required Protective Devices and Cable Cross-SectionsAlways connect the ground wire first Hardwire Connection of Output Power Cable to UPSConnection to Output Receptacles Connection of Extended Battery Module, UPS, and TransformerUPS Set-Up OperationInitial Start-Up Final Start-Up SequenceOperating Modes Normal modeECO mode Equipment is supplied in ECO modeEnd of backup time Operation on Battery PowerTransfer to battery power Low battery warningUPS Shutdown When on Battery UPS Shutdown When AC PresentReturn to Normal AC Source Access to Measurements Access to Maintenance and Personalization DataDisplay Organization UPS Set-Up Local SettingsOutput Settings ON/OFF SettingsUPS Set-Up Using External Software MaintenanceBattery Settings This page left blank intentionally 86-87050-00 A01 Displayed details Signification Correction TroubleshootingTroubleshooting Leds 21 Equipment is no longer protected by the UPSDisplay Signification Correction Power Module FaultLCM warning details Signification Life Cycle Monitoring LCMDescription Get free offersReset or disable LCM Secure your installation power continuityDisconnecting the battery sub-module MaintenanceHot Swapping the Power Sub-Module Hot Swapping the Battery Sub-Module86-87050-00 A01 Appendix Technical specificationsMGE Standard Single Phrase Warranty Technical Support and Product Services Pulsar MX Glossary Pulsar MX Page Scenic Avenue, Costa Mesa, California 92626 714 Contact MGE