Pulsar MX
Remote Power Off communication port (9)
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully
◗The output devices can be powered again through auto bypass when the
◗The output devices will remain powered < 1 sec. after RPO activation.
Push the start button to return to normal operation.
Note: The internal batteries will remain connected to the power
The cable is not included.Remote power off contact normally open (9)
Installation of optional |
|
communication card (66102) | RJ12 |
|
+
5 V DC to 27 V DC
_
Remote power off contact normally closed (9)
RJ12
+
5 VDC to 27 VDC
_
◗ Signal:
activation voltage: 5 V DC to 27 V DC,
current: 10 mA max.
2.6 Required Protective Devices and Cable Cross-Sections
Recommended upstream protection
UPS Power Rating | Upstream Circuit | |
Breaker | ||
| ||
5000 RT | D curve - 35A | |
|
|
2 poles circuit breaker
L1
L2 (N) To UPS Normal AC source
G L2 (N) L1
Required cable cross-sections
◗
◗Capacity for earthing conductor: 6 mm2 , solid or stranded wire (maximum AWG 10).
2 — 6 | Installation |