MGE UPS Systems 5000 RT user manual Return to Normal AC Source, UPS Shutdown When AC Present

Page 26

Pulsar MX

3.5 Return to Normal AC Source

After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalization) and the load is supplied again.

3.6 UPS Shutdown When AC Present

Before shutdown, please read ALL instructions below:

22

ON AUTO BYPASS

1.Press and hold the "0” (off) button (28) for 3 seconds. The buzzer beeps once.

The load is no longer protected by the UPS. It is powered via the Normal AC source (bypass). If the UPS is set in frequency converter mode, the equipment will not be powered. If the Normal AC source is out of tolerance, the UPS will generate a 10ms output calibrated break.

LEDs (22) is ON, LEDs (33) and (34) are green.

For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the off position or remove the Normal AC source.

33

34

28

3.7 UPS Shutdown When on Battery

Before shutdown, please read ALL instructions below:

NO

YES

1.Press and hold the "0” (off) button (28) for 3 seconds. The buzzer beeps once.

2.The display asks for confirmation.

3.Press the scroll button (25) to select yes.

4.Press confirm button (27).

The UPS is now fully shut down.

25

27

28

3 — 4

Operation

86-87050-00 A01

Image 26
Contents Pulsar MX Page Pulsar MX Pulsar MX Contents Technical Support and Product Services Return Policy for Repair of Single Phase Products RGAIntroduction Environmental protectionImportant Safety Instructions Symbol Usage This page left blank intentionally 86-87050-00 A01 Tower Position PresentationStandard Positions Rack PositionRear Panels Pulsar MX 5000 RT Pulsar MX EXB RT TransformerRack Mounting Kit Accessories for Rack MountDisplay and Control Panel Optional battery extension cable 6 ft/1.8 m Extended Battery EXBBattery Integration System Kit with Casters Battery extensions for Pulsar MX RTInstallation Unpacking and Contents CheckInternal Battery Connection Battery Start-up Installation in Tower PositionInstallation in Rack Position To adjust the display positionRear bracket system included with rail kits Connection to the communication port by relays Communication PortsConnection to the RS232 or USB communication port Required Protective Devices and Cable Cross-Sections Remote Power Off communication portInstallation of optional Communication card Recommended upstream protectionHardwire Connection of Output Power Cable to UPS Always connect the ground wire firstConnection of Extended Battery Module, UPS, and Transformer Connection to Output Receptacles Final Start-Up Sequence Operation Initial Start-Up UPS Set-UpEquipment is supplied in ECO mode Normal modeECO mode Operating ModesLow battery warning Operation on Battery PowerTransfer to battery power End of backup timeReturn to Normal AC Source UPS Shutdown When AC PresentUPS Shutdown When on Battery Display Organization Access to Maintenance and Personalization DataAccess to Measurements ON/OFF Settings Local SettingsOutput Settings UPS Set-UpBattery Settings MaintenanceUPS Set-Up Using External Software This page left blank intentionally 86-87050-00 A01 Equipment is no longer protected by the UPS TroubleshootingTroubleshooting Leds 21 Displayed details Signification CorrectionPower Module Fault Display Signification CorrectionGet free offers Life Cycle Monitoring LCMDescription LCM warning details SignificationSecure your installation power continuity Reset or disable LCMHot Swapping the Battery Sub-Module MaintenanceHot Swapping the Power Sub-Module Disconnecting the battery sub-module86-87050-00 A01 Technical specifications AppendixMGE Standard Single Phrase Warranty Technical Support and Product Services Pulsar MX Glossary Pulsar MX Page Contact MGE Scenic Avenue, Costa Mesa, California 92626 714