2.7Hardwire Connection of Output Power Cable to UPS

This type of connection must be carried out by qualified electrical personnel.

Before carrying out any connection, check that the battery circuit breaker and the upstream protection device (Normal AC source) is open "0" (off).

RS-232BATT.NO. RPO

 

TIO

N:

CAU

 

 

 

 

0V~,2

4A

200-25

 

 

 

1.Remove the top of the terminal box cover (2 screws) with the included screwdriver.

2.Insert the output cable/conduit (provided by others) through the cable knockout (2).

3.Connect the outlet cable to the output terminal block.

4.Tighten the cable/conduit flange and refit the terminal box cover by means of the 2 screws.

Always connect the ground wire first.

2 3

1

0 20

Note: 10’ Input cable with L6-30P (3) comes attached by MGE UPS SYSTEMS. Output cable/conduit (2) is not included (provided by others).

RS-232BATT.NO. RPO

 

TIO

N:

CAU

 

 

 

-250V

~,24A

 

Output Terminal

2

3

 

2 & 3

GND L2(N) L1

 

 

 

 

BATT.NO. RPO

 

 

 

 

RS-232

 

 

 

TIO

N:

 

 

CAU

 

 

 

0V~,2

4A

 

 

200-25

 

 

 

 

 

 

 

2 3

4

86-87050-00 A01

Installation

2 — 7

Image 21
Contents Pulsar MX Page Pulsar MX Pulsar MX Contents Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesEnvironmental protection IntroductionImportant Safety Instructions Symbol Usage This page left blank intentionally 86-87050-00 A01 Standard Positions PresentationTower Position Rack PositionPulsar MX 5000 RT Pulsar MX EXB RT Transformer Rear PanelsAccessories for Rack Mount Display and Control PanelRack Mounting Kit Battery Integration System Kit with Casters Extended Battery EXBOptional battery extension cable 6 ft/1.8 m Battery extensions for Pulsar MX RTUnpacking and Contents Check InstallationInstallation in Tower Position Internal Battery Connection Battery Start-upTo adjust the display position Installation in Rack PositionRear bracket system included with rail kits Communication Ports Connection to the RS232 or USB communication portConnection to the communication port by relays Installation of optional Communication card Remote Power Off communication portRequired Protective Devices and Cable Cross-Sections Recommended upstream protectionAlways connect the ground wire first Hardwire Connection of Output Power Cable to UPSConnection to Output Receptacles Connection of Extended Battery Module, UPS, and TransformerInitial Start-Up OperationFinal Start-Up Sequence UPS Set-UpECO mode Normal modeEquipment is supplied in ECO mode Operating ModesTransfer to battery power Operation on Battery PowerLow battery warning End of backup timeUPS Shutdown When AC Present UPS Shutdown When on BatteryReturn to Normal AC Source Access to Maintenance and Personalization Data Access to MeasurementsDisplay Organization Output Settings Local SettingsON/OFF Settings UPS Set-UpMaintenance UPS Set-Up Using External SoftwareBattery Settings This page left blank intentionally 86-87050-00 A01 Troubleshooting Leds 21 TroubleshootingEquipment is no longer protected by the UPS Displayed details Signification CorrectionDisplay Signification Correction Power Module FaultDescription Life Cycle Monitoring LCMGet free offers LCM warning details SignificationReset or disable LCM Secure your installation power continuityHot Swapping the Power Sub-Module MaintenanceHot Swapping the Battery Sub-Module Disconnecting the battery sub-module86-87050-00 A01 Appendix Technical specificationsMGE Standard Single Phrase Warranty Technical Support and Product Services Pulsar MX Glossary Pulsar MX Page Scenic Avenue, Costa Mesa, California 92626 714 Contact MGE