Installation and User Manual
Battery Settings
Function | Factory Setting | Options | Comments | |
|
|
|
| |
Auto Battery Test | Every week | No test / daily / monthly |
| |
|
|
|
| |
Low Batt warning | 20% | 0 to 100% | 1% increment | |
|
|
|
| |
| UPS reads number of |
|
| |
User Battery Settings | battery modules | From 0 to 40 Ah | 5 Ah increment | |
| connected |
|
| |
|
|
|
| |
Deep Discharge |
|
| Protection against deep | |
Yes | No | discharge. If disable, MGE UPS | ||
Protect | ||||
|
| SYSTEMS warranty will be void | ||
|
|
| ||
|
|
|
|
4.5 Maintenance
Function |
| Option/Display | Comments | |
|
|
|
| |
|
| SN: xxxxxxxxx | Serial number | |
Model | Power Module | SOFT: xxx | Soft version | |
|
| NT: xxx | Technical level | |
|
|
|
| |
|
| Description | 10 alarms can be stored | |
| Read | Date Hour | ||
Alarm History | automatically | |||
| Alarm xxx | |||
|
| |||
|
|
|
| |
| Erase | No / Yes |
| |
|
|
|
| |
Manual Batt Test | Manual Battery Test | No / Yes |
| |
|
|
|
| |
Led & Buzzer Test | Led & Buzzer Test | No / Yes |
| |
|
|
|
| |
Life Cycle Monitoring | LCM | Enable / Disable | Life cycling monitoring alarms | |
|
|
|
| |
| Auto Statistics | Statistics | You need to register at | |
Statistics |
|
| www.mgeups.com/Icm to get the | |
| Reset Date: No, Yes | |||
Custom Statistics | code and get access to free | |||
| ||||
| Statistics | statistics | ||
|
| |||
|
|
|
| |
Operation Limits | Operation Limits |
| Automatic alarms displayed when | |
| UPS is operating near the limits | |||
|
|
| ||
|
|
|
|
4.6 UPS Set-Up Using External Software
◗Insert the
◗ On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
◗Then select "Settings", "Advanced settings" and "UPS settings".
Note: This feature is only supported through Windows and the RS232 communication.
Access to Maintenance and | 4 — 3 | |
| Personalization Data |
|