Operation

3.1 Initial Start-Up

To ensure that your system is configured in complete accordance with safety regulations and to benefit from the manufacturer’s warranty, please contact Technical Support.

22

1. Check that the battery disconnect switch (60) on top cover is connected (see section 2.2 Internal Battery Connection).

2. Set the upstream circuit breaker (not included) to the on position.

The equipment is powered via the Normal AC source, but not protected by the UPS.

Batteries are recharging, an 8 hour recharge period is necessary to get full backup time.

LED (22) is ON, LEDs (33) and (34) are green.

33 34

UPS Set-Up

i

If UPS personalization is desired, it is advised to enter the personalization mode at this time (see the 4.4

"Personalization" section).

3.2 Final Start-Up Sequence

20 21 22

3. Press and hold the "I" (on) button (29) for 3 seconds.

The buzzer beeps once, and after UPS internal test sequence, the LED (20) is ON.

LEDs (30), (32), (34) are green.

The equipment is protected by the UPS.

If LED (21) or (22) is ON, an alarm has occurred (see the "troubleshooting" section).

30

32

34

29

86-87050-00 A01

Operation

3 — 1

Image 23
Contents Pulsar MX Page Pulsar MX Pulsar MX Contents Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesEnvironmental protection IntroductionImportant Safety Instructions Symbol Usage This page left blank intentionally 86-87050-00 A01 Rack Position PresentationStandard Positions Tower PositionPulsar MX 5000 RT Pulsar MX EXB RT Transformer Rear PanelsRack Mounting Kit Accessories for Rack MountDisplay and Control Panel Battery extensions for Pulsar MX RT Extended Battery EXBBattery Integration System Kit with Casters Optional battery extension cable 6 ft/1.8 mUnpacking and Contents Check InstallationInstallation in Tower Position Internal Battery Connection Battery Start-upTo adjust the display position Installation in Rack PositionRear bracket system included with rail kits Connection to the communication port by relays Communication PortsConnection to the RS232 or USB communication port Recommended upstream protection Remote Power Off communication portInstallation of optional Communication card Required Protective Devices and Cable Cross-SectionsAlways connect the ground wire first Hardwire Connection of Output Power Cable to UPSConnection to Output Receptacles Connection of Extended Battery Module, UPS, and TransformerUPS Set-Up OperationInitial Start-Up Final Start-Up SequenceOperating Modes Normal modeECO mode Equipment is supplied in ECO modeEnd of backup time Operation on Battery PowerTransfer to battery power Low battery warningReturn to Normal AC Source UPS Shutdown When AC PresentUPS Shutdown When on Battery Display Organization Access to Maintenance and Personalization DataAccess to Measurements UPS Set-Up Local SettingsOutput Settings ON/OFF SettingsBattery Settings MaintenanceUPS Set-Up Using External Software This page left blank intentionally 86-87050-00 A01 Displayed details Signification Correction TroubleshootingTroubleshooting Leds 21 Equipment is no longer protected by the UPSDisplay Signification Correction Power Module FaultLCM warning details Signification Life Cycle Monitoring LCMDescription Get free offersReset or disable LCM Secure your installation power continuityDisconnecting the battery sub-module MaintenanceHot Swapping the Power Sub-Module Hot Swapping the Battery Sub-Module86-87050-00 A01 Appendix Technical specificationsMGE Standard Single Phrase Warranty Technical Support and Product Services Pulsar MX Glossary Pulsar MX Page Scenic Avenue, Costa Mesa, California 92626 714 Contact MGE