Appendix
8.1 Technical specifications
| Pulsar MX 5000 |
| Pulsar MX EXB |
|
|
|
|
Output power | 5000 VA (1) / |
|
|
4500 W (2) |
|
| |
|
|
| |
|
|
|
|
Electrical supply network |
|
|
|
◗ Rated input voltage | Single phase 208 V |
|
|
◗ Input voltage range | 120/156 V to 280 V (3) |
|
|
◗ Frequency | 50/60 Hz (autoselect) |
|
|
◗ Power factor | > 0.99 |
|
|
◗ Leakage current | 7 mA |
|
|
|
|
|
|
Load output |
|
|
|
◗ Voltage | Single phase 208 V ±3% (4) |
|
|
◗ Frequency | 50/60 Hz ±0,5% (5) |
|
|
◗ Harmonic distortion | < 3% |
|
|
◗ Overload capacity | 105% continuous, 110% 2min, |
|
|
| 125% 1min, > 150% 0.5s |
|
|
|
|
|
|
| 15 x 12V - 5 Ah, |
| Two 15 x 12 V - 5 Ah |
Battery | sealed lead acid, |
| strings, sealed lead acid, |
| maintenance free |
| maintenance free |
|
|
|
|
Environment |
|
|
|
◗ Operating temperature range | 0°C to 40°C |
| |
◗ Relative humidity | 20% to 90% |
| |
◗ Storage temperature range |
| ||
◗ Altitude | 1000 m |
| |
|
|
| |
◗ Noise level | < 45 dBA |
|
|
|
|
|
|
(1)If the output voltage is 200V — 250V, the output power is 5000VA / 4500W.
(2)With one EXB module or more, the standard output power is 5000VA / 4000W.
(3)Values for 70% / 100% of UPS output.
(4)Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the Personal
(5)
(6)
Appendix | 8 — 1 |