Troubleshooting
5.1 Troubleshooting LEDS (21) and (22)
If LED (21) is ON:
The equipment is protected by the UPS but the operation is downgraded.
If LED (22) is ON:
The equipment is no longer protected by the UPS.
5.2 Troubleshooting Not Requiring MGE UPS SYSTEMS
ENVIRONMENT FAULT |
27
Press the "Enter" button (27) to display the details below:
Displayed details | Signification | Correction | |
|
|
| |
NO BATTERY | The battery is incorrectly connected | Check battery connections (see section 2.9) | |
|
|
| |
I/O BAD CONNECTION | AC source is not connected to the | Check AC wiring | |
correct terminals | |||
|
| ||
|
|
| |
NO POWER MODULE | The power | Check power | |
inserted | (see section 7.1) | ||
| |||
|
|
| |
NO BATTERY MODULE | The battery | Check battery connections (see section 7.2) | |
incorrectly connected | |||
|
| ||
|
|
| |
INV THERM OVERLOAD | The UPS shuts down automatically | Check the power drawn by the connected devices | |
because of a major overload | and disconnect any | ||
| |||
|
|
| |
INVERT LIMITATION | Short circuit conditions on output | Check the installation at the UPS output (wiring, fault | |
devices | equipment) | ||
| |||
|
|
|