Users Manual
1.4.2 Power Flow Diagrams
1.4.2.1 Normal Operation
During normal operation, power flows from the main AC input source (mains 1) into the UPS rectifier/battery charger section. The rectifier/battery charger converts the AC voltage to DC, maintains the charge of the battery, and feeds the DC power to the inverter. The inverter regenerates AC voltage, and supplies the attached load. See Figure
Figure 1-4: Normal Operation, Power Flow Diagram.
Static switch
Bypass AC input (mains 2)
Rectifier/battery | Inverter |
charger |
Main AC input (mains 1)
Attached load(s)
Battery
1.4.2.2 On-Battery Operation
If the main AC input source (mains 1) fails or goes out of tolerance, the charger stops. Power flows from the battery to the UPS inverter, which in turn supplies the attached load. When the main AC input source (mains 1) returns, the charger restarts automatically and the UPS resumes its normal operation. See Figure
If the battery becomes depleted before the main AC input source (mains 1) returns, the inverter stops and the attached load is transferred to the bypass AC input source (mains 2) if it is available.
Figure 1-5: On-Battery Operation, Power Flow Diagram.
Static switch
Bypass AC input (mains 2)
Rectifier/battery | Inverter |
charger |
Main AC input (mains 1)
Attached load(s)
Battery
Introduction | page 1 — 5 |