MGE UPS Systems EPS 7000 Alphanumeric Display and Controls, Settings Display Pushbutton

Page 18

EPS 7000 Single Module

Inverter on

(item 6) This green pushbutton is used to start the inverter. When it is pushed, the

 

green “load protected” LED flashes for three seconds, indicating that the start

 

command has been received. When the inverter has synchronized with the bypass

 

AC input (mains 2) source, the static switch transfers the load to the inverter output.

 

If the inverter cannot synchronize to the bypass AC input (mains 2) source, the load

 

must be forced to transfer using the hidden panel (see section 2.11, Forced

 

Transfers).

Inverter off

(item 7) This gray pushbutton is used to stop the inverter. When it is pressed for 3

 

seconds, the inverter stops and the load is transferred to the bypass AC input (mains

2)source. If the uninterrupted transfer conditions are not met, this pushbutton has no effect and the inverter can be stopped only from the hidden panel (see Section 2.12, Forced Transfers).

1.5.2Alphanumeric Display and Controls

The alphanumeric display is located directly below the front panel display. See Figure 1-7. For complete instructions, refer to section 2.0 Operation, Using the Alphanumeric Displays.

LCD

Settings

˘

display

pushbutton

pushbutton

LOAD IS PROTECTED UPS IS ON LINE

1 2 3

V

A W.Hz

+ –

45

!

6 7 8

*

A brief description of the display and controls follow.

Figure 1-8: Alphanumeric LCD Display , Settings , and Pushbutton Indicators and Controls.

Front Panel Alphanumeric Legend: (details on following page)

ø

ı

Settings

V

Voltage

A

Current

W.Hz Power/Frequency

Battery

Alarms

Ø

On/Off

*

Confirm/Verify

 

 

 

 

 

 

1.5.2.1 Two-line Alphanumeric Display

This 40-character, two line LCD displays general status of the UPS continuously, and displays measurements of UPS operating parameters as selected with the control pushbuttons.

page 1 — 8

Introduction

Image 18
Contents EPS Opening enclosures expose hazardous voltages. Always refer Service to qualified personnel onlyWith installation manual, may cause harmful interference to Louverture des cabinets expose des tensions dangereusesFor service call MGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714Revision History WarrantyService and Factory Repair Call Proprietary Rights StatementService personnel against possible equipment damage How To Use This ManualService personnel against safety hazards and possible Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Reference Manuals Section Descriptions MaintenanceScope IntroductionGeneral Description Specifications, Circuit Breakers and Powerflow Diagrams QF1Circuit Breaker Locations on the Maintenance Bypass Cabinet Power Flow Diagrams Normal Operation On-Battery OperationSingle Module Indicators and Controls Front Panel Alphanumeric Display Hidden Panel Cover PlateAudible alarm Front PanelSettings Display Pushbutton Alphanumeric Display and ControlsTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Hidden Panel Indicators Numbered LightsØOn/off LED Alphanumeric Indicators Reserved for future useAudible alarm reset Test connectorClear fault log Hidden Panel Lower PushbuttonsCertain the load can tolerate this interruption see section Using the forced transfer functions will cause the load toExperience an interruption for a minimum of 0.8 seconds. Be Forced TransfersThis page left blank intentionally Status Screen Display General status screenSelect English U.S. as the display language to match Settings Selection ScreenAlarms Displays as presented in this manualSensor Measurements Bypass V, HzVoltage Measurements RMSCurrent Measurements Load Crest FPower Frequency Measurements Load P1 P2 P3 KVABattery Measurements Battery Measurements DisplaysGeneral Alarms Secondary AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Preparations Before Start-up Checks Before Start-up Start-upProgrammed for automatic restart, the inverter will Automatically start after the battery disconnect circuitBecause it is standard for the UPS module to be Breaker QF1 has been closedWith Maintenance Bypass Normal ShutdownWithout Maintenance Bypass Maintenance bypass will disconnect the attached loadOpening Q4S with the inverter stopped in a UPS without Uninterrupted Transfer Conditions Forced Transfer from Bypass AC Input Source to InverterForced Transfer from Inverter to Bypass AC Input Leistungsfaehigkeit. Unbeabsichtigtes Schweissen und Gleichstrom zum Wechselrichter kommt gewoehnlich von derBatteriebank mit einer sehr hohen Kurzschluss Schwere Verbrennungen koennen die Folgevon fehlerhafterPreventive Maintenance Replacement PartsLevel Description Symbols Definition / Meaning O s s a r yIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557