MGE UPS Systems EPS 7000 user manual Preparations Before Start-up Checks Before Start-up

Page 36

EPS 7000 Single Module

2.10Preparations Before Start-up

Preparing before start-up uses a check list to powering up the EPS 7000. Reference the EPS 7000 Shared Systems Users Manual 86-134005-00, and Installation Manual for Single module and Shared Systems 86-134003-00, in conjunction with this start-up procedure, to utilize information of the controls and indicators during start-up.

2.10.1Checks Before Start-up

Before starting the EPS 7000, thoroughly read this manual to be certain that you fully understand the operation of the EPS 7000 Single Modules indicators, controls, and operational sequences.

Before starting the EPS 7000, make certain that these conditions exist (as applicable to your installation):

All power and control wires have been properly connected and securely tightened.

The upstream and downstream protective devices are not tripped, and have been sized properly for the UPS and load requirements.

The input voltage is the same as indicated on the UPS nameplate, located inside the left door of the EPS 7000 module.

The air filters located inside each EPS 7000 module front door are properly installed and free of dust, dirt, and debris. Make certain that no objects block the air intake around the front bottom of the enclosures, and that the air exhaust at the top rear of the enclosures is free of obstructions.

The UPS module input isolation circuit breaker Q1 is in the OFF (open) position.

The bypass circuit breaker Q4S is in the OFF (open) position.

The optional maintenance bypass circuit breaker Q3BP (if present) is in the OFF (open) position.

The optional UPS isolation circuit breaker Q5N (if present) is in the OFF (open) position.

The battery disconnect circuit breaker QF1 is in the OFF (open) position.

2.10.2Start-up

The following start-up procedure should be performed during the initial start-up following installation of the system, and this sequence should be followed any time that the EPS 7000 UPS is being restarted from an off condition (i.e., after the UPS has been powered down by removing the upstream AC input power and opening all the circuit breakers of the UPS).

a.Apply power to Q4S by closing the upstream circuit breaker supplying Q4S.

b.Apply power to the UPS input by closing the upstream circuit breaker supplying the main AC input (mains 1).

c.Close the optional maintenance bypass circuit breaker Q3BP (if present). Power is now available at the UPS output (the load is energized) via the bypass source.

d.Close the control or bypass circuit breaker Q4S. The static switch will come on-line; the fans will start.

e.Close the output isolation circuit breaker Q5N (if present).

f.Open the maintenance bypass circuit breaker Q3BP (if present). The load is now supplied via the bypass source.

Note that if your UPS configuration does not include the maintenance bypass option, start-up requires only closing Q4S to supply the bypass source to the attached load.

page 2 —12

Operation

Image 36
Contents EPS Service to qualified personnel only With installation manual, may cause harmful interference toOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesFor service call MGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714Warranty Service and Factory Repair CallRevision History Proprietary Rights StatementHow To Use This Manual Service personnel against safety hazards and possibleService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Maintenance ScopeReference Manuals Section Descriptions IntroductionGeneral Description Specifications, Circuit Breakers and Powerflow Diagrams QF1Circuit Breaker Locations on the Maintenance Bypass Cabinet Power Flow Diagrams Normal Operation On-Battery OperationSingle Module Indicators and Controls Front Panel Alphanumeric Display Hidden Panel Cover PlateAudible alarm Front PanelSettings Display Pushbutton Alphanumeric Display and ControlsTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Hidden Panel Indicators Numbered LightsØOn/off LED Alphanumeric Indicators Reserved for future useTest connector Clear fault logAudible alarm reset Hidden Panel Lower PushbuttonsUsing the forced transfer functions will cause the load to Experience an interruption for a minimum of 0.8 seconds. BeCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally Status Screen Display General status screenSettings Selection Screen AlarmsSelect English U.S. as the display language to match Displays as presented in this manualSensor Measurements Bypass V, HzVoltage Measurements RMSCurrent Measurements Load Crest FPower Frequency Measurements Load P1 P2 P3 KVABattery Measurements Battery Measurements DisplaysGeneral Alarms Secondary AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Preparations Before Start-up Checks Before Start-up Start-upAutomatically start after the battery disconnect circuit Because it is standard for the UPS module to beProgrammed for automatic restart, the inverter will Breaker QF1 has been closedWith Maintenance Bypass Normal ShutdownWithout Maintenance Bypass Maintenance bypass will disconnect the attached loadOpening Q4S with the inverter stopped in a UPS without Uninterrupted Transfer Conditions Forced Transfer from Bypass AC Input Source to InverterForced Transfer from Inverter to Bypass AC Input Gleichstrom zum Wechselrichter kommt gewoehnlich von der Batteriebank mit einer sehr hohen KurzschlussLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterPreventive Maintenance Replacement PartsLevel Description Symbols Definition / Meaning O s s a r yIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557