MGE UPS Systems EPS 7000 Hidden Panel Lower Pushbuttons, Test connector, Clear fault log

Page 22

EPS 7000 Single Module

I: Battery discharged

This orange LED indicates that the battery has reached the end of its autonomy, shutting down the inverter.

J: Inverter desynchronized

This orange LED indicates that the inverter is not synchronized with the bypass AC input (mains 2).

K: Transfer fault

This red LED indicates a transfer fault, which may be one or more of the following conditions:

Inverter output static switch fault

Static switch over-temperature

Static switch power supply fault

Transfer control board fault

Power supply board fault

L: Overload

This orange LED indicates an alarm condition resulting from one or more of the following conditions:

Inverter current above rating

Output current above rating

Inverter and/or static switch shutdown due to excessive load current

M: Bypass AC input (mains 2) outside tolerance

This orange LED indicates that the bypass AC input (mains 2) voltage and/or frequency are too high or too low.

N: Maintenance position

This orange LED indicates that circuit breakers QF1, Q4S, Q5N, or Q3BP are set to the maintenance position. The UPS is not available for load protection.

1.5.3.2Hidden Panel Lower Pushbuttons

Following are brief descriptions of the function of the hidden panel pushbuttons. See Figure 1-9.

Test connector

(port) This 9-pin connector is reserved for service. It is used to connect the cabinet

 

to a computer, allowing system calibration, personalization, and computer-aided

 

diagnostics.

Clear fault log

Pressing this pushbutton clears the alarms stored in memory, allowing the unit to

 

restart. Memorized alarms cannot be cleared until the condition causing the alarm

 

has been corrected.

Audible alarm reset

Pressing this pushbutton stops the audible alarm. Should a new fault condition at a

 

higher alarm level occur, the alarm will sound again.

Battery charge cycle

(pushbutton #1) Pressing this pushbutton begins a battery charging cycle. After the

 

cycle is complete, the rectifier/battery charger returns to float charge levels on the

 

battery. The battery charge cycle is not applicable to sealed lead-acid battery instal-

 

lations.

page 1 — 12

Introduction

Image 22
Contents EPS Opening enclosures expose hazardous voltages. Always refer Service to qualified personnel onlyWith installation manual, may cause harmful interference to Louverture des cabinets expose des tensions dangereusesFor service call MGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714Revision History WarrantyService and Factory Repair Call Proprietary Rights StatementService personnel against possible equipment damage How To Use This ManualService personnel against safety hazards and possible Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Reference Manuals Section Descriptions MaintenanceScope IntroductionGeneral Description Specifications, Circuit Breakers and Powerflow Diagrams QF1Circuit Breaker Locations on the Maintenance Bypass Cabinet Power Flow Diagrams Normal Operation On-Battery OperationSingle Module Indicators and Controls Front Panel Alphanumeric Display Hidden Panel Cover PlateAudible alarm Front PanelAlphanumeric Display and Controls Settings Display PushbuttonTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Numbered Lights Hidden Panel IndicatorsØOn/off LED Alphanumeric Indicators Reserved for future useAudible alarm reset Test connectorClear fault log Hidden Panel Lower PushbuttonsCertain the load can tolerate this interruption see section Using the forced transfer functions will cause the load toExperience an interruption for a minimum of 0.8 seconds. Be Forced TransfersThis page left blank intentionally Status Screen Display General status screenSelect English U.S. as the display language to match Settings Selection ScreenAlarms Displays as presented in this manualSensor Measurements Bypass V, HzVoltage Measurements RMSCurrent Measurements Load Crest FPower Frequency Measurements Load P1 P2 P3 KVABattery Measurements Battery Measurements DisplaysSecondary Alarms General AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Preparations Before Start-up Checks Before Start-up Start-upProgrammed for automatic restart, the inverter will Automatically start after the battery disconnect circuitBecause it is standard for the UPS module to be Breaker QF1 has been closedWith Maintenance Bypass Normal ShutdownMaintenance bypass will disconnect the attached load Without Maintenance BypassOpening Q4S with the inverter stopped in a UPS without Forced Transfer from Bypass AC Input Source to Inverter Uninterrupted Transfer ConditionsForced Transfer from Inverter to Bypass AC Input Leistungsfaehigkeit. Unbeabsichtigtes Schweissen und Gleichstrom zum Wechselrichter kommt gewoehnlich von derBatteriebank mit einer sehr hohen Kurzschluss Schwere Verbrennungen koennen die Folgevon fehlerhafterReplacement Parts Preventive MaintenanceLevel Description Symbols Definition / Meaning O s s a r yIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557