MGE UPS Systems EPS 7000 user manual Using the forced transfer functions will cause the load to

Page 23

 

 

 

 

Users Manual

 

 

 

 

 

 

 

 

Return to float voltage

(pushbutton #2) This pushbutton can be used during a battery charge cycle to force

 

 

 

the rectifier/battery charger back to the float voltage level.

 

 

Security pushbutton

(key) This pushbutton must be pressed simultaneously with any of the following

 

 

 

three pushbuttons. This helps guard against inadvertent transfer of the load with

 

 

 

interruption.

 

 

Inverter desync/sync

(pushbutton #3) Pressing and holding the “security key” while pressing this

 

 

 

pushbutton forces the inverter output to desynchronize or synchronize to the bypass

 

 

 

AC input (mains 2) source.

 

 

Forced bypass to inverter

(pushbutton #4) Pressing and holding the “security key” while pressing this

 

 

 

pushbutton forces the transfer of the load to the inverter output when the bypass is

 

 

 

out of tolerance. The inverter must be on; press the “inverter on” pushbutton on the

 

 

 

UPS front panel if necessary. The load will experience a 0.8 second interruption.

 

 

 

Refer to section 2.12, Forced Transfers.

 

 

Forced inverter to bypass

(pushbutton #5) Pressing and holding the “security key” while pressing this

 

 

 

pushbutton stops the inverter and transfers the load to the bypass AC input (mains

 

 

 

2) even if the bypass is out of tolerance. The load will experience a 0.8 second inter-

 

 

 

ruption. Refer to section 2.12, Forced Transfers.

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION:

 

Using the forced transfer functions will cause the load to

 

 

 

 

experience an interruption for a minimum of 0.8 seconds. Be

 

 

 

 

certain the load can tolerate this interruption; see section

 

 

 

 

2.12 Forced Transfers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Introduction

page 1 — 13

Image 23
Contents EPS Louverture des cabinets expose des tensions dangereuses Service to qualified personnel onlyWith installation manual, may cause harmful interference to Opening enclosures expose hazardous voltages. Always referMGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714 For service callProprietary Rights Statement WarrantyService and Factory Repair Call Revision HistoryEquipment feature How To Use This ManualService personnel against safety hazards and possible Service personnel against possible equipment damageUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Introduction MaintenanceScope Reference Manuals Section DescriptionsGeneral Description QF1 Specifications, Circuit Breakers and Powerflow DiagramsCircuit Breaker Locations on the Maintenance Bypass Cabinet On-Battery Operation Power Flow Diagrams Normal OperationFront Panel Alphanumeric Display Hidden Panel Cover Plate Single Module Indicators and ControlsFront Panel Audible alarmTwo-line Alphanumeric Display Settings Display PushbuttonAlphanumeric Display and Controls Alphanumeric Display Pushbuttons ØOn/off Hidden Panel IndicatorsNumbered Lights Reserved for future use LED Alphanumeric IndicatorsHidden Panel Lower Pushbuttons Test connectorClear fault log Audible alarm resetForced Transfers Using the forced transfer functions will cause the load toExperience an interruption for a minimum of 0.8 seconds. Be Certain the load can tolerate this interruption see sectionThis page left blank intentionally General status screen Status Screen DisplayDisplays as presented in this manual Settings Selection ScreenAlarms Select English U.S. as the display language to matchBypass V, Hz Sensor MeasurementsRMS Voltage MeasurementsLoad Crest F Current MeasurementsLoad P1 P2 P3 KVA Power Frequency MeasurementsBattery Measurements Displays Battery MeasurementsLCD Messages General AlarmsSecondary Alarms Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Start-up Preparations Before Start-up Checks Before Start-upBreaker QF1 has been closed Automatically start after the battery disconnect circuitBecause it is standard for the UPS module to be Programmed for automatic restart, the inverter willNormal Shutdown With Maintenance BypassOpening Q4S with the inverter stopped in a UPS without Without Maintenance BypassMaintenance bypass will disconnect the attached load Forced Transfer from Inverter to Bypass AC Input Uninterrupted Transfer ConditionsForced Transfer from Bypass AC Input Source to Inverter Schwere Verbrennungen koennen die Folgevon fehlerhafter Gleichstrom zum Wechselrichter kommt gewoehnlich von derBatteriebank mit einer sehr hohen Kurzschluss Leistungsfaehigkeit. Unbeabsichtigtes Schweissen undLevel Description Preventive MaintenanceReplacement Parts O s s a r y Symbols Definition / MeaningIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557