Page 37

Users Manual

g.Close the input isolation circuit breaker Q1. Verify that the following conditions exist:

The red “load not protected” LED is on

The rectifier/battery charger automatically starts

If either condition is not present, there is a fault. Open Q1 and contact MGE Customer Support Services.

h.Close the battery disconnect circuit breaker QF1. The batteries are now connected to the rectifier/battery charger, and have begun charging.

IMPORTANT:

Because it is standard for the UPS module to be

 

programmed for automatic restart, the inverter will

 

automatically start after the battery disconnect circuit

 

breaker QF1 has been closed.

 

 

i.If the UPS is not programmed for automatic restart, press the “inverter on” pushbutton. The green “load protected” LED will flash for about 3 seconds, indicating that the inverter is starting.

j.The UPS will automatically transfer the load to the UPS inverter output. The green “load protected” LED will turn on and remain on.

NOTE:

If the transfer conditions are not satisfied (bypass AC input

 

sources is out of tolerance) a forced transfer is required.

 

Refer to section 2.12 Forced Transfers.

 

 

 

 

2.10.3Checks After Start-up

After initial start-up of the system, normal operation should be tested. At the minimum, the following tests should be performed as applicable to your installation:

Emergency power off (EPO) test.

Remote emergency power off (REPO) test (if applicable).

Inverter start and stop.

Battery transfer test.

Maintenance bypass procedure.

2.11Shutdown

Shutdown procedures in this section apply to the EPS 7000 cabinet under normal, emergency, overload, and mainte- nance conditions.

Operation

page 2 —13

Image 37
Contents EPS With installation manual, may cause harmful interference to Service to qualified personnel onlyOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesMGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714 For service callService and Factory Repair Call WarrantyRevision History Proprietary Rights StatementService personnel against safety hazards and possible How To Use This ManualService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Scope MaintenanceReference Manuals Section Descriptions IntroductionGeneral Description QF1 Specifications, Circuit Breakers and Powerflow DiagramsCircuit Breaker Locations on the Maintenance Bypass Cabinet On-Battery Operation Power Flow Diagrams Normal OperationFront Panel Alphanumeric Display Hidden Panel Cover Plate Single Module Indicators and ControlsFront Panel Audible alarmAlphanumeric Display and Controls Settings Display PushbuttonTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Numbered Lights Hidden Panel IndicatorsØOn/off Reserved for future use LED Alphanumeric IndicatorsClear fault log Test connectorAudible alarm reset Hidden Panel Lower PushbuttonsExperience an interruption for a minimum of 0.8 seconds. Be Using the forced transfer functions will cause the load toCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally General status screen Status Screen DisplayAlarms Settings Selection ScreenSelect English U.S. as the display language to match Displays as presented in this manualBypass V, Hz Sensor MeasurementsRMS Voltage MeasurementsLoad Crest F Current MeasurementsLoad P1 P2 P3 KVA Power Frequency MeasurementsBattery Measurements Displays Battery MeasurementsSecondary Alarms General AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Start-up Preparations Before Start-up Checks Before Start-upBecause it is standard for the UPS module to be Automatically start after the battery disconnect circuitProgrammed for automatic restart, the inverter will Breaker QF1 has been closedNormal Shutdown With Maintenance BypassMaintenance bypass will disconnect the attached load Without Maintenance BypassOpening Q4S with the inverter stopped in a UPS without Forced Transfer from Bypass AC Input Source to Inverter Uninterrupted Transfer ConditionsForced Transfer from Inverter to Bypass AC Input Batteriebank mit einer sehr hohen Kurzschluss Gleichstrom zum Wechselrichter kommt gewoehnlich von derLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterReplacement Parts Preventive MaintenanceLevel Description O s s a r y Symbols Definition / MeaningIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557