MGE UPS Systems EPS 7000 user manual Battery Cabinet Overtemp

Page 33

Users Manual

LOAD ON

BYPASS !

This message indicates that the load has been transferred to the bypass AC input (mains 2) source. The load is no longer protected.

BYPASS PROBLEM

CHECK FREQUENCY !

This message indicates that the bypass AC input (mains 2) source is out of frequency tolerance. The inverter has switched to free-running mode. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.

BYPASS PROBLEM

CHECK VOLTAGE !

This message indicates that the bypass AC input (mains 2) source is out of voltage tolerance. The inverter has switched to free-running mode. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.

INDEPENDENT INVERTER

FREQ. COMMAND ON !

This message indicates that the inverter has been set to free-running mode. The inverter is not synchronized to the bypass AC input (mains 2) power source. Transfer of the load from the inverter output to the bypass AC input source requires an interruption of power to the load.

BYPASS TRANSFER

LOCKOUT COMMAND ON !

This message indicates that the UPS has been set not to transfer from the inverter to the bypass AC input (mains 2) source. In the event of an inverter shutdown, the load will be disconnected.

BATTERY CABINET

OVERTEMP. !

This message indicates that the ambient temperature of the battery is out of tolerance.

UPS INPUT PROBLEM

CHECK FREQUENCY !

This message indicates that the main AC input (mains 1) frequency is out of tolerance. The rectifier/battery charger has shut down and the inverter is operating from its battery source.

UPS INPUT PROBLEM

CHECK VOLTAGE !

This message indicates that the main AC input (mains 1) voltage is out of tolerance. the rectifier/battery charger has shut down and the inverter is operating from its battery source.

CHARGER SHUTDOWN

COMMAND ON !

This message indicates that the rectifier/battery charger has been instructed to shut down, for example during progressive (stepped) transfer to a motor-generator set.

Operation

page 2 —9

Image 33
Contents EPS With installation manual, may cause harmful interference to Service to qualified personnel onlyOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesMGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714 For service callService and Factory Repair Call WarrantyRevision History Proprietary Rights StatementService personnel against safety hazards and possible How To Use This ManualService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Scope MaintenanceReference Manuals Section Descriptions IntroductionGeneral Description QF1 Specifications, Circuit Breakers and Powerflow DiagramsCircuit Breaker Locations on the Maintenance Bypass Cabinet On-Battery Operation Power Flow Diagrams Normal OperationFront Panel Alphanumeric Display Hidden Panel Cover Plate Single Module Indicators and ControlsFront Panel Audible alarmSettings Display Pushbutton Alphanumeric Display and ControlsTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Hidden Panel Indicators Numbered LightsØOn/off Reserved for future use LED Alphanumeric IndicatorsClear fault log Test connectorAudible alarm reset Hidden Panel Lower PushbuttonsExperience an interruption for a minimum of 0.8 seconds. Be Using the forced transfer functions will cause the load toCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally General status screen Status Screen DisplayAlarms Settings Selection ScreenSelect English U.S. as the display language to match Displays as presented in this manualBypass V, Hz Sensor MeasurementsRMS Voltage MeasurementsLoad Crest F Current Measurements Load P1 P2 P3 KVA Power Frequency MeasurementsBattery Measurements Displays Battery MeasurementsGeneral Alarms Secondary AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Start-up Preparations Before Start-up Checks Before Start-upBecause it is standard for the UPS module to be Automatically start after the battery disconnect circuitProgrammed for automatic restart, the inverter will Breaker QF1 has been closedNormal Shutdown With Maintenance BypassWithout Maintenance Bypass Maintenance bypass will disconnect the attached loadOpening Q4S with the inverter stopped in a UPS without Uninterrupted Transfer Conditions Forced Transfer from Bypass AC Input Source to InverterForced Transfer from Inverter to Bypass AC Input Batteriebank mit einer sehr hohen Kurzschluss Gleichstrom zum Wechselrichter kommt gewoehnlich von derLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterPreventive Maintenance Replacement PartsLevel Description O s s a r y Symbols Definition / MeaningIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557