MGE UPS Systems EPS 7000 user manual Uninterrupted Transfer Conditions

Page 40

EPS 7000 Single Module

3.Wait for the green LED “B” on the hidden panel to turn on (indicating that the rectifier/battery charger has started), then close the battery disconnect circuit breaker QF1. If there is more than one battery cabinet in your configuration, close all the battery disconnect circuit breakers.

4.Automatic restart of the UPS is the normal configuration; the UPS inverter will start automatically and resume normal operation. If your EPS 7000 has been programmed NOT to automatically restart, start the inverter by pressing the “inverter on” pushbutton on the UPS front panel. In a few moments, the inverter will start and the UPS will resume normal operation. If the transfer conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required. Refer to section 2.12, Forced Transfers.

2.12Forced Transfers

This section describes the normal transfer conditions and the procedures to be followed when issuing forced transfers.

CAUTION:

Opening Q4S with the inverter stopped in a UPS without

 

maintenance bypass will disconnect the attached load.

 

 

 

 

2.12.1Uninterrupted Transfer Conditions

To transfer the load between the UPS module output and the bypass AC input (mains 2) source without interruption, the following conditions must be satisfied:

inverter output and bypass AC input phases must be in sync

Bypass AC input voltage must be within 10% of nominal

Bypass AC input frequency must be within a certain programmable tolerance of nominal

Provided that both the UPS module output and bypass AC input sources meet these conditions, uninterrupted transfers can take place. If these conditions are not met, transfers cannot take place without interruption. A forced transfer is required.

Forced transfers require a power interruption to the load of 0.8 seconds. Before issuing a forced transfer command, be certain that the attached load can tolerate the brief outage. The following paragraphs describe the forced transfer procedures.

2.12.2Forced Transfer from Bypass AC Input Source to Inverter

Start the inverter by pressing the “inverter on” button on the front panel.

On the hidden panel, press the “security” key and hold it while pressing the “forced bypass to inverter” key (pushbutton #4). The load will be disconnected for 0.8 seconds, then connected to the inverter.

2.12.3Forced Transfer from Inverter to Bypass AC Input

On the hidden panel, press the “security” key and hold it while pressing the “forced inverter to bypass” key (pushbutton #5). The inverter will stop and the load will be disconnected for 0.8 seconds; then the load will be connected to the bypass AC input source.

page 2 —16

Operation

Image 40
Contents EPS Service to qualified personnel only With installation manual, may cause harmful interference toOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesFor service call MGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714Warranty Service and Factory Repair CallRevision History Proprietary Rights StatementHow To Use This Manual Service personnel against safety hazards and possibleService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Maintenance ScopeReference Manuals Section Descriptions IntroductionGeneral Description Specifications, Circuit Breakers and Powerflow Diagrams QF1Circuit Breaker Locations on the Maintenance Bypass Cabinet Power Flow Diagrams Normal Operation On-Battery OperationSingle Module Indicators and Controls Front Panel Alphanumeric Display Hidden Panel Cover PlateAudible alarm Front PanelAlphanumeric Display and Controls Settings Display PushbuttonTwo-line Alphanumeric Display Alphanumeric Display Pushbuttons Numbered Lights Hidden Panel IndicatorsØOn/off LED Alphanumeric Indicators Reserved for future useTest connector Clear fault logAudible alarm reset Hidden Panel Lower PushbuttonsUsing the forced transfer functions will cause the load to Experience an interruption for a minimum of 0.8 seconds. BeCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally Status Screen Display General status screenSettings Selection Screen AlarmsSelect English U.S. as the display language to match Displays as presented in this manualSensor Measurements Bypass V, HzVoltage Measurements RMSCurrent Measurements Load Crest FPower Frequency Measurements Load P1 P2 P3 KVABattery Measurements Battery Measurements DisplaysSecondary Alarms General AlarmsLCD Messages Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Preparations Before Start-up Checks Before Start-up Start-upAutomatically start after the battery disconnect circuit Because it is standard for the UPS module to beProgrammed for automatic restart, the inverter will Breaker QF1 has been closedWith Maintenance Bypass Normal ShutdownMaintenance bypass will disconnect the attached load Without Maintenance BypassOpening Q4S with the inverter stopped in a UPS without Forced Transfer from Bypass AC Input Source to Inverter Uninterrupted Transfer ConditionsForced Transfer from Inverter to Bypass AC Input Gleichstrom zum Wechselrichter kommt gewoehnlich von der Batteriebank mit einer sehr hohen KurzschlussLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterReplacement Parts Preventive MaintenanceLevel Description Symbols Definition / Meaning O s s a r yIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557