MGE UPS Systems EPS 7000 user manual LCD Messages, General Alarms, Secondary Alarms

Page 32

EPS 7000 Single Module

2.9 LCD Messages

This section presents the most common alarm messages that appear on the LCD (the alphanumeric section of the “hidden” panel), and explains their meaning.

LOAD IS PROTECTED

UPS IS ON LINE

This is the normal display message. There are no alarms or problems, and the load is being supplied by the UPS inverter.

2.9.1General Alarms

LOW LEVEL ALARM

UPS OK !

This message indicates that a problem requiring action has occurred. The load is still supplied by the inverter. The problem is listed in the secondary alarm message (see below), as indicated by the flashing exclamation mark (!). The alarm message may be viewed by pressing the “alarm” pushbutton (!)

UPS INPUT FAILURE

LOAD ON BATTERY !

This message indicates that the main AC input (mains 1) has failed or is outside of tolerance, and power to the inverter is being supplied from the UPS battery system. The load is still supplied via the inverter.

REMAINING BAT. TIME __ MN %KW LOAD = __

This message is automatically displayed every five seconds when the UPS is on battery. It alternates with the previous message. The message provides an estimate of the available remaining time on battery, based on the percentage of full rated load being supplied, the type of battery, the battery temperature, and the battery age.

UPS LOW BATTERY

SHUTDOWN IMMINENT !

This message indicates that the batteries have reached the “low battery shutdown” warning level. The user must take steps to prepare the load for shutdown (load shedding, file saving and computer shutdown, etc.). This message replaces the previous two messages when the batteries are nearly depleted. When this message appears, there are only a few minutes of battery back-up time remaining.

UPS ALARM

CALL SERVICE !

This indicates that the battery disconnect circuit breaker QF1 has been open or the inverter has stopped and that service is required. The problem is listed in the secondary alarm message (see below), as indicated by the flashing exclamation mark (!). The secondary alarm message may be viewed by pressing the “alarm” pushbutton (!).

2.9.2Secondary Alarms

The presence of these alarms is indicated by a flashing exclamation mark (!) on the general alarm message. Press the “alarm” pushbutton to view these messages.

EMERGENCY SHUTDOWN

REPO ON !

This message indicates that the UPS has been shut down because a remote emergency power off (REPO) pushbutton has been pressed and is still closed.

page 2 —8

Operation

Image 32
Contents EPS Service to qualified personnel only With installation manual, may cause harmful interference toOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesFor service call MGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714Warranty Service and Factory Repair CallRevision History Proprietary Rights StatementHow To Use This Manual Service personnel against safety hazards and possibleService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Maintenance ScopeReference Manuals Section Descriptions IntroductionGeneral Description Specifications, Circuit Breakers and Powerflow Diagrams QF1Circuit Breaker Locations on the Maintenance Bypass Cabinet Power Flow Diagrams Normal Operation On-Battery OperationSingle Module Indicators and Controls Front Panel Alphanumeric Display Hidden Panel Cover PlateAudible alarm Front PanelTwo-line Alphanumeric Display Settings Display PushbuttonAlphanumeric Display and Controls Alphanumeric Display Pushbuttons ØOn/off Hidden Panel IndicatorsNumbered Lights LED Alphanumeric Indicators Reserved for future useTest connector Clear fault logAudible alarm reset Hidden Panel Lower PushbuttonsUsing the forced transfer functions will cause the load to Experience an interruption for a minimum of 0.8 seconds. BeCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally Status Screen Display General status screenSettings Selection Screen AlarmsSelect English U.S. as the display language to match Displays as presented in this manualSensor Measurements Bypass V, HzVoltage Measurements RMS Current Measurements Load Crest FPower Frequency Measurements Load P1 P2 P3 KVABattery Measurements Battery Measurements DisplaysLCD Messages General AlarmsSecondary Alarms Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Preparations Before Start-up Checks Before Start-up Start-upAutomatically start after the battery disconnect circuit Because it is standard for the UPS module to beProgrammed for automatic restart, the inverter will Breaker QF1 has been closedWith Maintenance Bypass Normal ShutdownOpening Q4S with the inverter stopped in a UPS without Without Maintenance BypassMaintenance bypass will disconnect the attached load Forced Transfer from Inverter to Bypass AC Input Uninterrupted Transfer ConditionsForced Transfer from Bypass AC Input Source to Inverter Gleichstrom zum Wechselrichter kommt gewoehnlich von der Batteriebank mit einer sehr hohen KurzschlussLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterLevel Description Preventive MaintenanceReplacement Parts Symbols Definition / Meaning O s s a r yIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557