M a i n t e n a n c e

3.0Scope

This section describes maintenance of the EPS 7000, including safety instructions, preventive maintenance, isolation for maintenance, information about replacement parts, and troubleshooting LCD alarm messages.

3.1Safety Instructions

WARNING:

DC input power to the inverter is normally from a battery

 

bank with a very high short-circuit capacity. Accidental

 

welding and severe burns can be caused by mistakes while

 

connecting or disconnecting these conductors.

ATTENTION

L'entrée DC de l'onduleur est normalement alimentée par une

 

batterie avee un courant de court-circuit élevé. Une erreur

 

lors de la connexion ou deconnexion de ces conducteurs

 

peut causer des soudures accidentelles et des brûlures

 

sérieuses.

WARNUNG!

Gleichstrom zum Wechselrichter kommt gewoehnlich von der

 

Batteriebank mit einer sehr hohen Kurzschluss

 

Leistungsfaehigkeit. Unbeabsichtigtes Schweissen und

 

schwere Verbrennungen koennen die Folgevon fehlerhafter

 

Verbindung und Trennung sein.

 

 

 

 

3.2IMPORTANT SAFETY INSTRUCTIONS FOR SERVICING BATTERIES

A.Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

B.When replacing batteries, use the same model and manufacturer of batteries.

C.CAUTION — Do not dispose of battery or batteries in a fire. The battery may explode.

D.CAUTION — Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

E.CAUTION — A battery can present a risk of electrical shock and high short-circuit current. The following precau- tions should be observed when working with batteries:

1.Remove watches, rings, or other metal objects.

2.Use tools with insulated handles.

3.Wear rubber gloves and boots.

4.Do not lay tools or metal parts on top of batteries.

5.Disconnect charging source prior to connecting or disconnecting battery terminals.

6.Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.

Maintenance

page 3 —1

Image 41
Contents EPS With installation manual, may cause harmful interference to Service to qualified personnel onlyOpening enclosures expose hazardous voltages. Always refer Louverture des cabinets expose des tensions dangereusesMGE UPS SYSTEMS, Inc Scenic Avenue Costa Mesa, CA 92626 714 For service callService and Factory Repair Call WarrantyRevision History Proprietary Rights StatementService personnel against safety hazards and possible How To Use This ManualService personnel against possible equipment damage Equipment featureUPS Unit Serial Number MBP Cabinet Serial Number N t e n t EPS 7000 Single Module Operation Figures This page left blank intentionally Scope MaintenanceReference Manuals Section Descriptions IntroductionGeneral Description QF1 Specifications, Circuit Breakers and Powerflow DiagramsCircuit Breaker Locations on the Maintenance Bypass Cabinet On-Battery Operation Power Flow Diagrams Normal OperationFront Panel Alphanumeric Display Hidden Panel Cover Plate Single Module Indicators and ControlsFront Panel Audible alarmTwo-line Alphanumeric Display Settings Display PushbuttonAlphanumeric Display and Controls Alphanumeric Display Pushbuttons ØOn/off Hidden Panel IndicatorsNumbered Lights Reserved for future use LED Alphanumeric IndicatorsClear fault log Test connectorAudible alarm reset Hidden Panel Lower PushbuttonsExperience an interruption for a minimum of 0.8 seconds. Be Using the forced transfer functions will cause the load toCertain the load can tolerate this interruption see section Forced TransfersThis page left blank intentionally General status screen Status Screen DisplayAlarms Settings Selection ScreenSelect English U.S. as the display language to match Displays as presented in this manualBypass V, Hz Sensor MeasurementsRMS Voltage MeasurementsLoad Crest F Current MeasurementsLoad P1 P2 P3 KVA Power Frequency MeasurementsBattery Measurements Displays Battery MeasurementsLCD Messages General AlarmsSecondary Alarms Battery Cabinet Overtemp Charger OFF Inverter Shutdown Thermal Overload a Start-up Preparations Before Start-up Checks Before Start-upBecause it is standard for the UPS module to be Automatically start after the battery disconnect circuitProgrammed for automatic restart, the inverter will Breaker QF1 has been closedNormal Shutdown With Maintenance BypassOpening Q4S with the inverter stopped in a UPS without Without Maintenance BypassMaintenance bypass will disconnect the attached load Forced Transfer from Inverter to Bypass AC Input Uninterrupted Transfer ConditionsForced Transfer from Bypass AC Input Source to Inverter Batteriebank mit einer sehr hohen Kurzschluss Gleichstrom zum Wechselrichter kommt gewoehnlich von derLeistungsfaehigkeit. Unbeabsichtigtes Schweissen und Schwere Verbrennungen koennen die Folgevon fehlerhafterLevel Description Preventive MaintenanceReplacement Parts O s s a r y Symbols Definition / MeaningIEC LCD Spdt Volts This page left blank intentionally Reorder form Scenic Avenue Costa Mesa, CA Page Page Scenic Avenue, Costa Mesa, California 92626 714 557