MGE UPS Systems 3000 VA, 2000 user manual Install, Power and equipment connections

Page 18

2. Installation

Install

This type of connection must be carried out by qualified electrical personnel.

Before carrying out any connections, check that the battery circuit breaker 8 is OFF and that the upstream protection devices (AC distribution system) are open (OFF).

8

32

33

Earthing wires

5Output terminal block

4Input terminal block

The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.

 

Pulsar EXtreme

Pulsar EXtreme

 

2000

3000

 

 

 

Cable diameter

From 9 to 12 mm

From 9 to 12 mm

 

 

 

Cross-sectional area of each wire

1 to 4 mm2

1,5 to 4 mm2

Recommended upstream

 

 

circuit breaker

 

 

Nominal rating

C60N 10A 2P

C60N 16A 2P

(47 to 63Hz, 230V)

(maximum line

(maximum line

 

current = 9A)

current = 13A)

Maximum rating

C60N 16A 2P

C60N 20A 2P

(47 to 63Hz, 187V)

(maximum line

(maximum line

 

current = 11A)

current = 16A)

 

 

 

Power and equipment connections:

1.Remove the terminal-block cover 32 .

2.Insert the cable supplying the equipment and the power cable through the cable clamps 33 .

3.Connect the three wires of the equipment cable to the output terminal block 5 .

Always connect the earthing wire first.

4.Connect the three wires of the power cable to the input terminal block 4 .

5.Refit the terminal-block cover.

6.Tighten the nut on the cable clamp 33 .

Page 18 - 51033211EN/AC

Image 18
Contents Pulsar EXtreme Introduction Using this document ForewordPictograms Contents Failure of AC input power and operation on battery power Glossary IndexTower model PresentationPulsar EXtreme range Rack modelConnection modules Fault tolerantHot swap Install Output terminal block with cable clampBack Battery extensions for UPS backup times of 66 minutes OptionsCLA Alarms Battery Load Remaining Control panelInstallation CD ROM with Solution Pac and UPS Driver softwaresUnpacking and checks Rack model Installation of the rack version Rack mounting diagram with railsInstallation of the communications-card option Connection to the RS 232 communications port optionalSecuring the connection modules Securing and connecting the connection modulesConnection to the AC-power source Two screwsAlways connect the earthing wire first Hot swapConnection of equipment to a terminal block Power and equipment connections ON-LINE operating mode OperationStart-up Bargraph indicationsFailure of AC input power and operation on battery power Function Personalizable function Default settingPersonalization On / OFF conditions tabOutput tab Battery tabPersonalizable function Default setting Options By-pass tabConnected equipment is no longer supplied with power ShutdownMaintenance Troubleshooting26 51033211EN/AC UPS replacement Fault-tolerant connection moduleConnected equipment is again protected by the UPS Hot-swap and Install connection modules Press button 24 and wait 20 seconds Check that LED 21 is on This product has been designed to respect the environment UPS recycling at the end of service lifeEnvironment PackingAppendices GlossarySleep mode InstallON-LINE mode Start on battery powerBattery Index34 51033211EN/AC