4. Maintenance

Hot-swap and Install connection modules

Before turning the switch,

see the manual

NORMAL

BY-PASS

3

20

bypass

21

24

Before turning the switch,

see the manual

NORMAL

BY-PASS

Disconnection:

1.Turn the manual bypass switch 3 , located behind the UPS (see section 2.5), from the NORMAL

to the intermediate position.

2.Check that LED 21 is ON before continuing to the BYPASS position.

If LED 21 is not ON, do not switch to the BYPASS position and call the after-sales support department.

3.Turn the manual bypass switch 3 from the intermediate position to the BYPASS position.

The connected equipment is supplied by the AC- power source, via the manual bypass.

4.Shut down the UPS by pressing button 24 (return to the OFF position).

5.Open the battery circuit breaker(s) 8 .

6.Remove the two fixing screws 31 and the connection module from the electronic module (see next page).

The UPS can be replaced. The connected equipment is supplied by the AC-power source.

Page 28 - 51033211EN/AC

Image 28
Contents Pulsar EXtreme Introduction Foreword Using this documentPictograms Contents Failure of AC input power and operation on battery power Glossary IndexPresentation Pulsar EXtreme rangeTower model Rack modelFault tolerant Hot swap InstallConnection modules Output terminal block with cable clampBack Battery extensions for UPS backup times of 66 minutes OptionsCLA Alarms Battery Load Remaining Control panelCD ROM with Solution Pac and UPS Driver softwares InstallationUnpacking and checks Rack model Installation of the rack version Rack mounting diagram with railsInstallation of the communications-card option Connection to the RS 232 communications port optionalSecuring and connecting the connection modules Connection to the AC-power sourceSecuring the connection modules Two screwsHot swap Always connect the earthing wire firstConnection of equipment to a terminal block Power and equipment connections ON-LINE operating mode OperationStart-up Bargraph indicationsFailure of AC input power and operation on battery power Personalizable function Default setting PersonalizationFunction On / OFF conditions tabBattery tab Personalizable function Default setting OptionsOutput tab By-pass tabConnected equipment is no longer supplied with power ShutdownMaintenance Troubleshooting26 51033211EN/AC Fault-tolerant connection module UPS replacementConnected equipment is again protected by the UPS Hot-swap and Install connection modules Press button 24 and wait 20 seconds Check that LED 21 is on UPS recycling at the end of service life EnvironmentThis product has been designed to respect the environment PackingAppendices GlossaryInstall ON-LINE modeSleep mode Start on battery powerBattery Index34 51033211EN/AC