4. Maintenance
Troubleshooting requiring MGE
Indication | Signification | Correction |
|
|
|
LED 15 flashes and the buzzer | UPS electronics have detected a UPS | For UPSs equipped with Hot |
beeps. | fault. | swap or Install connection |
| Depending on the UPS personalization | modules, follow the UPS |
| parameters (see section 3.5), there are | replacement procedure (see |
| two possibilities: | section 4.2). |
| ◗the equipment connected to the UPS |
|
| continues to be supplied, but directly | Call the |
| from the | department. |
| automatic bypass for a maximum of 8 |
|
| hours (LED 21 ON); |
|
| ◗the connected equipment is no longer |
|
| supplied. |
|
| The equipment connected to |
|
| the UPS is no longer protected. |
|
|
|
|
LED 16 flashes. | A battery fault was detected during the | Call the |
| battery test. | department because the |
|
| batteries need replacing. |
|
|
|