MGE UPS Systems 2000, 3000 VA Press button 24 and wait 20 seconds Check that LED 21 is on

Page 29

20

21

22

24

8

10

31 3

31

4. Maintenance

Reconnection:

1.Insert the connection module in the connector 10 and secure using the two screws 31 .

2.Switch the battery circuit breaker(s) 8 to the ON position and check that LED 20 is ON.

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).

3.Press button 24 and wait 20 seconds.

4.Check that LED 21 is ON.

If LED 21 is not ON, do not switch to the intermediate position and call the after-sales support department.

5.Turn the manual bypass switch 3 from the BYPASS position to the intermediate position and check that LED 20 is ON.

6.Turn the manual bypass switch 3 from the intermediate position to the NORMAL position. LED 21 goes OFF and LED 22 goes ON.

The connected equipment is again protected by the UPS.

51033211EN/AC - Page 29

Image 29
Contents Pulsar EXtreme Introduction Pictograms Using this documentForeword Contents Glossary Index Failure of AC input power and operation on battery powerPulsar EXtreme range PresentationTower model Rack modelHot swap Install Fault tolerantConnection modules Output terminal block with cable clampBack Options Battery extensions for UPS backup times of 66 minutesCLA Control panel Alarms Battery Load RemainingUnpacking and checks InstallationCD ROM with Solution Pac and UPS Driver softwares Rack model Rack mounting diagram with rails Installation of the rack versionConnection to the RS 232 communications port optional Installation of the communications-card optionConnection to the AC-power source Securing and connecting the connection modulesSecuring the connection modules Two screwsConnection of equipment to a terminal block Always connect the earthing wire firstHot swap Power and equipment connections Operation ON-LINE operating modeBargraph indications Start-upFailure of AC input power and operation on battery power Personalization Personalizable function Default settingFunction On / OFF conditions tabPersonalizable function Default setting Options Battery tabOutput tab By-pass tabShutdown Connected equipment is no longer supplied with powerTroubleshooting Maintenance26 51033211EN/AC Connected equipment is again protected by the UPS UPS replacementFault-tolerant connection module Hot-swap and Install connection modules Press button 24 and wait 20 seconds Check that LED 21 is on Environment UPS recycling at the end of service lifeThis product has been designed to respect the environment PackingGlossary AppendicesON-LINE mode InstallSleep mode Start on battery powerIndex Battery34 51033211EN/AC