American Power Conversion MatrixTM UPS user manual Replacing or Adding Battery Packs

Page 32

7.4 Replacing or Adding Battery Packs

You can expect to receive 3 to 6 years of service life from the Battery Packs when installed in a cool, dry location. The Battery Pack's life is shortened when operated in an environment where the ambient temperature is normally above 30°C (86°F).

The Electronics Unit will display this message when any one of the connected Battery Packs requ Battery Packs that can no longer sustain a charge are identified by an illuminated Replace Battery

Battery Packs can be added or replaced at any time, regardless of mode of operation. See the procedures listed below to replace a worn Battery Pack.

Caution: If the first Battery Pack in the string (connected directly the Electronics Unit) is replaced, the UPS will not be able to support the load in the event of a utility failure during the time that the battery string is uncoupled from the EU. Always place the UPS in bypass when this Battery Pack is replaced.

7.4.1Disconnect both INPUT and OUTPUT battery communications cables connected at the worn Battery Pack.

7.4.2Remove the clamps securing the in-line coupler and panel coupler (if necessary) at the worn Battery Pack.

7.4.3Unmate the couplers at the worn Battery Pack and return it to the factory for recycling.

7.4.4If necessary, remove the panel coupler clamp. Set the new Battery Pack in place.

7.4.5Mate the in-line and panel couplers on the new Battery Pack.

7.4.6Secure the couplers with the coupler clamps.

7.4.7Plug-in the battery communications cables at the new Battery Pack. See the illustration in section 4.9.6.

Note: Always check the number of Battery Packs reported by the UPS (UPS Status menu) after a Battery Packs.

Note: If this fault message is encountered, check the communications cables to, and from each B section 4.9.6.

Image 32 Contents
American Power Conversion MatrixTM UPS User’s ManualTable of Contents Emergency Power Off EPO IntroductionOverview Hot Swappable ModulesRemote Interfaces SafetyDisplay Presentation Isolation Unit IU5a. Nema 5-15R receptacles Electronics Unit EU Rear View of the Electronics UnitBattery Pack Rear ViewProtection Strategies InstallationReceiving Inspection Input Voltage Selection PlacementMoving the UPS Vac Input Configuration Module InterconnectionsTypical installation showing mated battery couplers Emergency Power Off EPO Interface Start-Up Modes of Operation OperationInput Plug Incompatibility Sleep Mode Standby modeOn-line mode On-battery modeBypass mode Default screensDisplay and Controls Operation Transfer between modes of operationUPS Control menu UPS Status menuUPS Diagnostics menu Page UPS Setup Page Page Password protection UPS TestsInterface Kits PowerChute SoftwareUPS Monitoring Computer Interface Port Difficulty Troubleshooting Chart Replace Electronics Unit EU Fault MessagesUPS requires service Battery status Replacing the Electronics Unit Replacing or Adding Battery Packs Obtaining Service Specifications Storing the UPSNoise and Surge Isolation EnvironmentPhysical ApprovalsTypical On-Battery Run Times 10.69 13.13 15.57 18.0111.56