American Power Conversion MatrixTM UPS user manual Battery Pack, Rear View

Page 8

6. Battery communications jack

The Battery Pack communications cable from the Battery Pack OUTPUT is connected at this jack.

7. Manual bypass switch

Pressing the manual bypass switch causes the UPS to transfer to the bypass mode of operation. While in this mode, the load is supplied with power conditioned by the IU. However, the load will not be protected from utility voltage sags, swells or blackouts. The EU is removed for service when the UPS is operating in bypass. See the Operation section of this manual for more details on this mode of operation.

8. Emergency Power Off jack

For applications where, for safety reasons, power to all room equipment must be cut off, the UPS provides a remote Emergency Power Off interface. A modular 6 position plug with offset latch fits this jack. See the Installation section of this manual for instructions on how to connect to the jack.

3.3 Battery Pack

Rear View

Front View

1. Battery Pack

The Battery Pack contains four series connected nominal 12 Vdc high-capacity sealed lead-acid batteries. Built-in ultra- low power consumption battery pack voltage and current monitoring electronics report pack status to the UPS. To conserve battery capacity, the internal electronics are shut down when the battery communications cable is not connected to the UPS, or when the UPS is not running.

2. INPUT battery communications jack

This input accepts battery status signals from the OUTPUT of another Battery Pack in the system. No connection is made to this jack in a single Battery Pack system.

3. OUTPUT battery communications jack

The Battery Pack sends status signals to the UPS or to the INPUT of another Battery Pack (in a multiple Battery Pack system) from this jack.

Image 8 Contents
American Power Conversion MatrixTM UPS User’s ManualTable of Contents Emergency Power Off EPO IntroductionOverview Hot Swappable ModulesRemote Interfaces SafetyDisplay Presentation Isolation Unit IU5a. Nema 5-15R receptacles Electronics Unit EU Rear View of the Electronics UnitBattery Pack Rear ViewProtection Strategies InstallationReceiving Inspection Input Voltage Selection PlacementMoving the UPS Vac Input Configuration Module InterconnectionsTypical installation showing mated battery couplers Emergency Power Off EPO Interface Start-Up Modes of Operation OperationInput Plug Incompatibility Sleep Mode Standby modeOn-line mode On-battery modeBypass mode Default screensDisplay and Controls Operation Transfer between modes of operationUPS Control menu UPS Status menuUPS Diagnostics menu Page UPS Setup Page Page Password protection UPS TestsInterface Kits PowerChute SoftwareUPS Monitoring Computer Interface Port Difficulty Troubleshooting Chart Replace Electronics Unit EU Fault MessagesUPS requires service Battery status Replacing the Electronics Unit Replacing or Adding Battery Packs Obtaining Service Specifications Storing the UPSNoise and Surge Isolation EnvironmentPhysical ApprovalsTypical On-Battery Run Times 10.69 13.13 15.57 18.0111.56