American Power Conversion MatrixTM UPS Typical On-Battery Run Times, 10.69 13.13 15.57 18.01

Page 36

9.9 Typical On-Battery Run Times

Typical On-Battery Run Time Versus Load, 3000 VA Matrix-UPS with SmartCells, in Hours

 

 

 

 

 

 

 

 

 

Number of SmartCells

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Computer Load

1

2

3

4

5

6

 

7

 

8

 

 

(VA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

3.07

7.20

11.56

15.93

20.29

24.65

 

29.02

 

33.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

1.46

3.52

5.80

8.24

10.69

13.13

 

15.57

 

18.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

0.57

1.46

2.46

3.52

4.58

5.80

 

7.02

 

8.24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

0.33

0.83

1.46

2.11

2.81

3.52

 

4.23

 

4.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

0.22

0.57

0.99

1.46

1.93

2.46

 

2.99

 

3.52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

0.17

0.46

0.78

1.18

1.59

1.99

 

2.45

 

2.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

0.13

0.36

0.62

0.92

1.25

1.59

 

1.92

 

2.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recharge Time, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

2.8

2.7

3.8

4.9

6

 

7

 

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times.

 

 

 

 

 

Run times are typical at 25° C (77° F).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recharge times to 90% of rated capacity after discharge into 50% of rated load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Typical On-Battery Run Time Versus Load, 3000 VA Matrix-UPS with SmartCell XR Battery Packs, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of SmartCell XR Battery Packs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Computer Load

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

 

(VA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

3

 

6.75

 

10.75

 

14.75

 

18.75

 

22.75

 

26.75

 

30.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

 

1.8

 

4.3

 

6.9

 

9.5

 

12.1

 

14.7

 

17.3

 

19.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

1.2

 

3

 

5

 

7

 

9

 

11

 

13

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

0.9

 

2.4

 

4

 

5.6

 

7.2

 

8.8

 

10.4

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

0.75

 

1.8

 

3.25

 

4.7

 

6.15

 

7.6

 

9.05

 

10.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recharge Time, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.8

 

8.1

 

12.5

 

16.9

 

21.3

 

25.7

 

30.1

 

34.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times. Run times are typical at 25° C (77° F).

Recharge times to 90% of rated capacity after discharge into 50% of rated load.

Image 36 Contents
American Power Conversion MatrixTM UPS User’s ManualTable of Contents Emergency Power Off EPO IntroductionOverview Hot Swappable ModulesSafety DisplayRemote Interfaces Presentation Isolation Unit IU5a. Nema 5-15R receptacles Electronics Unit EU Rear View of the Electronics UnitBattery Pack Rear ViewInstallation Receiving InspectionProtection Strategies Placement Moving the UPSInput Voltage Selection Vac Input Configuration Module InterconnectionsTypical installation showing mated battery couplers Emergency Power Off EPO Interface Start-Up Operation Input Plug IncompatibilityModes of Operation Sleep Mode Standby modeOn-line mode On-battery modeBypass mode Default screensDisplay and Controls Operation Transfer between modes of operationUPS Control menu UPS Status menuUPS Diagnostics menu Page UPS Setup Page Page Password protection UPS TestsPowerChute Software UPS MonitoringInterface Kits Computer Interface Port Difficulty Troubleshooting Chart Fault Messages UPS requires serviceReplace Electronics Unit EU Battery status Replacing the Electronics Unit Replacing or Adding Battery Packs Obtaining Service Specifications Storing the UPSNoise and Surge Isolation EnvironmentPhysical ApprovalsTypical On-Battery Run Times 10.69 13.13 15.57 18.0111.56