American Power Conversion MatrixTM UPS user manual Replacing the Electronics Unit

Page 31

7.3 Replacing the Electronics Unit

The UPS allows replacement of a failed Electronics Unit without interruption of power to the load.

The Isolation Unit is capable of autonomous operation and provides power to the load isolated from

EMI/RFI noise and surges.

To replace a failed EU, follow the procedures listed below.

7.3.1Put the UPS into the bypass mode of operation by actuating the manual bypass switch at the rear of the EU. Note: Transfers to bypass mode using the manual bypass switch occur within 10 mS typically. The transfer back from the bypass mode occurs in 0 mS.

7.3.2Using a coin or large flat blade screwdriver, unscrew the EU separating screw and pull back.

7.3.3Using a Phillips screwdriver, loosen the Battery Pack coupler lock at the rear of the EU and disconnect the pack coupler. Disconnect the Battery Pack communications cable from the jack at the rear of the EU.

7.3.4If necessary, disconnect cables connected at the computer interface port and the Emergency Power Off interface.

7.3.5Grasp the EU at the slots shown in the illustration and pull straight up and away from the IU.

7.3.6Follow the above procedures in reverse to install the replacement EU. Once the replacement EU is installed, press any key to regain control of the UPS.

Image 31 Contents
MatrixTM UPS User’s Manual American Power ConversionTable of Contents Hot Swappable Modules Emergency Power Off EPOIntroduction OverviewDisplay SafetyRemote Interfaces Isolation Unit IU Presentation5a. Nema 5-15R receptacles Rear View of the Electronics Unit Electronics Unit EURear View Battery PackReceiving Inspection InstallationProtection Strategies Moving the UPS PlacementInput Voltage Selection Module Interconnections Vac Input ConfigurationTypical installation showing mated battery couplers Emergency Power Off EPO Interface Start-Up Input Plug Incompatibility OperationModes of Operation On-battery mode Sleep ModeStandby mode On-line modeTransfer between modes of operation Bypass modeDefault screens Display and Controls OperationUPS Status menu UPS Control menuUPS Diagnostics menu Page UPS Setup Page Page UPS Tests Password protectionUPS Monitoring PowerChute SoftwareInterface Kits Computer Interface Port Difficulty Troubleshooting Chart UPS requires service Fault MessagesReplace Electronics Unit EU Battery status Replacing the Electronics Unit Replacing or Adding Battery Packs Obtaining Service Storing the UPS SpecificationsApprovals Noise and Surge IsolationEnvironment Physical10.69 13.13 15.57 18.01 Typical On-Battery Run Times11.56