American Power Conversion MatrixTM UPS user manual 11.56

Page 37

Typical On-Battery Run Time Versus Load, 5000 VA Matrix-UPS with SmartCells, in Hours

 

 

 

 

Number of SmartCells

 

 

 

 

 

 

 

 

 

 

 

Computer Load

2

3

4

 

5

6

7

8

(VA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

3.07

5.02

7.20

 

9.38

11.56

13.75

15.93

 

 

 

 

 

 

 

 

 

1000

1.46

2.46

3.52

 

4.58

5.80

7.02

8.24

 

 

 

 

 

 

 

 

 

1500

0.83

1.46

2.11

 

2.81

3.52

4.23

4.99

 

 

 

 

 

 

 

 

 

2000

0.57

0.99

1.46

 

1.93

2.46

2.99

3.52

 

 

 

 

 

 

 

 

 

2500

0.46

0.78

1.18

 

1.59

1.99

2.45

2.90

 

 

 

 

 

 

 

 

 

3000

0.36

0.62

0.92

 

1.25

1.59

1.92

2.30

 

 

 

 

 

 

 

 

 

4000

0.24

0.42

0.62

 

0.83

1.08

1.33

1.59

 

 

 

 

 

 

 

 

 

5000

0.17

0.31

0.46

 

0.62

0.78

0.98

1.18

 

 

 

 

 

 

 

 

 

 

 

Recharge Time, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

2.8

2.7

3.8

 

4.9

6

7

8.1

 

 

 

 

 

 

 

 

 

The case of one SmartCell does not apply to 5000 VA Matrix-UPS.

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times. Run times are typical at 25° C (77° F).

Recharge times to 90% of rated capacity after discharge into 50% of rated load.

Typical On-Battery Run Time Versus Load, 5000 VA Matrix-UPS with SmartCell XR Battery Packs, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of SmartCell XR Battery Packs

 

 

 

 

 

 

 

 

 

 

 

 

 

Computer Load

1

2

3

4

5

6

7

 

8

(VA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

3

6.75

10.75

14.75

18.75

22.75

26.75

 

30.75

 

 

 

 

 

 

 

 

 

 

1500

1.8

4.3

6.9

9.5

12.1

14.7

17.3

 

19.9

 

 

 

 

 

 

 

 

 

 

2000

1.2

3

5

7

9

11

13

 

15

 

 

 

 

 

 

 

 

 

 

2500

0.9

2.4

4

5.6

7.2

8.8

10.4

 

12

 

 

 

 

 

 

 

 

 

 

3000

0.75

1.8

3.25

4.7

6.15

7.6

9.05

 

10.5

 

 

 

 

 

 

 

 

 

 

4000

0.53

1.25

2.25

3.25

4.25

5.25

6.25

 

7.25

 

 

 

 

 

 

 

 

 

 

5000

0.37

0.9

1.6

2.4

3.2

4

4.8

 

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recharge Time, in Hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.8

8.1

12.5

16.9

21.3

25.7

30.1

 

34.5

 

 

 

 

 

 

 

 

 

 

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times. Run times are typical at 25° C (77° F).

Recharge times to 90% of rated capacity after discharge into 50% of rated load.

Image 37 Contents
MatrixTM UPS User’s Manual American Power ConversionTable of Contents Introduction Emergency Power Off EPOOverview Hot Swappable ModulesDisplay SafetyRemote Interfaces Isolation Unit IU Presentation5a. Nema 5-15R receptacles Rear View of the Electronics Unit Electronics Unit EURear View Battery PackReceiving Inspection InstallationProtection Strategies Moving the UPS PlacementInput Voltage Selection Module Interconnections Vac Input ConfigurationTypical installation showing mated battery couplers Emergency Power Off EPO Interface Start-Up Input Plug Incompatibility OperationModes of Operation Standby mode Sleep ModeOn-line mode On-battery modeDefault screens Bypass modeDisplay and Controls Operation Transfer between modes of operationUPS Status menu UPS Control menuUPS Diagnostics menu Page UPS Setup Page Page UPS Tests Password protectionUPS Monitoring PowerChute SoftwareInterface Kits Computer Interface Port Difficulty Troubleshooting Chart UPS requires service Fault MessagesReplace Electronics Unit EU Battery status Replacing the Electronics Unit Replacing or Adding Battery Packs Obtaining Service Storing the UPS SpecificationsEnvironment Noise and Surge IsolationPhysical Approvals10.69 13.13 15.57 18.01 Typical On-Battery Run Times11.56