Specifications
InfraStruXure PDU
Electrical | With Transformer | Without Transformer |
| |
|
|
|
|
|
Output |
|
|
|
|
Voltage AC | L1, L2, L3, N, PE | 400/230V: 3W, N, PE |
| |
Full Load Rating | 60kVA | 100A |
| |
Nominal Current | 167A | 180A |
| |
Number of Distribution Panels | 2 × 225A, |
|
|
|
Max. Distribution Breaker Size | 150AT | 150AT |
| |
Main Breaker | 175A MCCB, 100% rated | 225A MCCB |
| |
Input |
|
|
|
|
Nominal Voltage | 400V | 400/230V |
| |
Frequency |
| |||
Voltage AC | L1, L2, L3, PE | 400/230V: 3W, N, PE (WYE) |
| |
Nominal Current | 167A | 100A |
| |
Disconnect | 225A molded case switch | N/A |
| |
|
|
|
|
|
Physical |
|
|
|
|
|
|
|
|
|
Dimensions (H×W ×D) |
|
|
|
|
PDU | 2159 × 610 × 864 mm | 2159 × 610 × 864 mm |
| |
| (85 × 24 × 34in) | (85 × 24 × 34in) |
| |
Weight |
|
|
|
|
PDU only | 410kg (904lb) | 204kg (450lb) |
| |
PDU with 28 cables | 556kg (1226lb) | 351kg (774lb) |
| |
|
|
|
|
|
Relay Outputs |
|
|
|
|
|
|
|
|
|
Nominal switching capacity | 1A at 30VDC |
|
|
|
Maximum switching power | 30W |
|
|
|
Maximum switching voltage | 60VDC |
|
|
|
Maximum switching current | 2ADC |
|
|
|
Maximum carrying current | 2ADC |
|
|
|
Surge Ratings | 2kV per Bellcore |
| ||
| 1.5kV per FCC part 68 |
|
|
|
|
|
|
|
|