Customizing and Updating the PDU
c.Observe the EPO LEDs. If the switch is wired and working properly, when the switch is engaged, both of the EPO state LEDs are red.
d.If the test was successful, place the Arm/Test rocker switch back to the Arm position. The PDU display interface will clear the EPO test mode alarm. If the test was not successful, see the troubleshooting chart:
Problem | Action |
|
|
Neither state LED was red when | • Check the wiring to your EPO switch. |
EPO switch was engaged | • Check to make sure the EPO DIP |
| switch configuration is correct for your |
| switch (NO or NC). See step 1 on the |
| previous page for proper configuration |
| instructions. |
|
|
Only one of the state LEDs was | • Check to make sure the EPO DIP |
red when the EPO switch was | switch configuration is correct for your |
engaged | switch (NO or NC) and test again. See |
| step 1 on the previous page for proper |
| configuration instructions. |
| • If the switch is configured correctly |
| and both LEDs are not red after testing |
| again, contact customer support at a |
| number on the back cover of this |
| manual. |
|
|
e. Repeat this test for each EPO switch installed.
3.Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.
Emergency Power Off (EPO)
This InfraStruXure PDU is provided with an Emergency Power Off switch connection. When this EPO switch is energized, electrical power to the units is
EPO can be achieved with either a contact closure or application of an external 24VAC or 24VDC from a SELV or PELV source. It’s important to note that hazardous voltage from the Mains voltage must be isolated from the contact closure or 24 VAC, 24 VDC. The EPO circuit contact closure, the 24VAC or the 24VDC are considered a SELV circuit as defined in EN 60950 Safety of Information Technology Equipment or PELV circuit as defined in IEC
60kW InfraStruXure | 51 |