Outback Power Systems FW-SP-ACA manual FW-SP-R Replacement for the FW-SP-250

Page 16

FW-SP-R (REPLACEMENT) for the FW-SP-250

In the event an FW-SP-250’s board is damaged, it can be replaced without going to the expense of

replacing the cover as well.

Tools Required to Install:

Purpose:

Slotted screwdriver

Wiring to the AC wiring block

Phillips screwdriver

Remove and install covers

• 13 mm socket (torque ratchet)

• Securing wires to FX DC terminals

Procedure: Be sure all AC and DC power to the FX is shut off before installing the FW-SP-250.

(3)Remove the FW-SP-250 (secured by six Phillips screws).

(2)Remove the AC Wiring Compartment cover (secured by two Phillips screws).

(1)Remove the DCC or Turbo cover (secured by four Phillips screws) and the DC battery caps.

(4)Remove the damaged FLEXware Surge Protector by unfastening these four Philips screws.

(5)The new FW-SP-R installs on these four standoffs on the inside of the FW-SP-250 cover; torque to 8-12 inch- pounds.

(6)When the new surge protector board has been secured to the FW-SP-250 cover, reinstall the FW-SP-250 as shown on pages 10-11.

15

Image 16
Contents Includes Mounting and Installation Surge ProtectorDisclaimer About OutBack Power SystemsContact Information Warranty Introduction Dear OutBack CustomerOutback FLEXware Surge Protector ModelsIntroduction Electrical Connections and LED Indicators FLEXware Surge Protector SpecificationsLEDs MountingTools Required to Install Purpose ProcedureRemoving and installing FX M5 hex bolts Underside screw secures FW-SP-ACA to FXRemove these Two M5 hex bolts from the FX Removing various covers from the FXPreparing and installing the FW-SP-ACA onto an FX FW-SP-ACA slides onto the FXFW-SP-ACA slides down FX slots Screws included secure the FW-SP-ACA to an FXFW-SP-250 FW-SP-250FW250 to check the placement of wires and components Procedure FW-SP-R Replacement for the FW-SP-ACA or the FW-ACAFW-ACA housing Locating pin Figures 12 FW-SP-R and FW-ACA Bracket FW-SP-R LEDsFW-SP-R installed inside the FW-ACA LED labelFW-SP-R Replacement for the FW-SP-250 Securing wires to FX DC terminalsWiring and Connecting the FLEXware Surge Protector FLEXware Surge Protector Wiring DesignationsSystem can now be powered up FLEXware Surge Protector Limited Warranty Revision Arlington, WA Surge Protector Limited Warranty RegistrationSystem Owner 19009 62nd Avenue NE +34