Carrier 50TCA04-A07 Smoke Detector Locations, Completing Installation of Return Air Smoke Sensor

Page 15

For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition.

Smoke Detector Locations

Supply Air — The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 18. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-off filter panel.

Smoke Detector Sensor

C08245

Fig. 18 - Typical Supply Air Smoke Detector Sensor

Location

Return Air without Economizer — The sampling tube is located across the return air opening on the unit basepan. See Fig. 19. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.)

Return Air Detector module (shipping position shown)*

Controller module

Return Air Detector Sampling Tube

*RA detector must be moved from shipping position to operating position by installer

C07307

Fig. 19 - Typical Return Air Detector Location

Return Air with Economizer — The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 20. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps below.)

50TC

Return Air

Sampling Tube

C08129

Fig. 20 - Return Air Sampling Tube Location

Completing Installation of Return Air Smoke Sensor:

Screws

Flexible

Exhaust Tubes

Sample Tube

C08126

Fig. 21 - Return Air Detector Shipping Position

1.Unscrew the two screws holding the Return Air Sensor detector plate. See Fig 21. Save the screws.

2.Remove the Return Air Sensor and its detector plate.

3.Rotate the detector plate so the sensor is facing out- wards and the sampling tube connection is on the bot- tom. See Fig 22.

4.Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the ex- haust tube is on the top. See Fig 22.

5.Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.

15

Image 15
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessRoutine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionSupply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Two-Row Coils Cleaning Condenser CoilRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Evaporator CoilCoreMax Access Port Assembly To Use Cooling Charging ChartsCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Condenser-Fan Location Troubleshooting Cooling SystemCompressor Filter DrierProblem Cause Remedy Cooling Service AnalysisSmoke Detectors Convenience OutletsSystem ControllerSensor Smoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseDirty Sensor Test Sensor and Controller Tests Sensor Alarm TestController Alarm Test Dirty Controller TestChanging the Dirt Sensor Test Detector CleaningRemote Test/Reset Station Dirty Sensor Test Cleaning the Smoke DetectorControl or Indicator Description IndicatorsAlarm State Detector IndicatorsProtective Devices TroubleshootingCondenser Fan Motor Protection Electric HeatersRelief Device Control CircuitTypical Single Point Installation Completing Heater InstallationPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic Temp Resistance 55 Space Temperature Sensor WiringTemperature Enthalpy Sensor PremierLink Sensor UsageOutdoor AIR Return AIR TB1 Terminal Field Connection Input Signal Space Sensor ModeThermostat Mode Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Tions Indoor CO2 Sensor 33ZCSENCO2 ConnecManufacturer CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables Color Code RecommendationsPremierLink CCN Bus Connections Economizer SystemsRUN Inputs OutputsEconoMi$er IV Control Modes Supply Air Temperature SAT SensorEconoMi$er Outdoor Air Lockout SensorOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Enthalpy Changeover SetpointsThermostats Exhaust Setpoint AdjustmentMinimum Position Control Damper MovementCO2 Sensor Configuration Demand Control Ventilation DCVEconoMi$er IV Sensor Usage Single Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionPRE-START-UP START-UP, Premierlink Controls START-UP, GeneralOperating Sequence, Base Unit Controls Memory ResetPerform System Check-Out Initial Operation and TestOperating Sequence, PremierLink Control 50TC Number Stages Economizer Available Cooling StagesOAT ≤ SPT 50TC 50TC Loadshed Command Gas and Electric Heat Units Fastener Torque ValuesLinkage Modes Torque Values 50TC Typical Unit Wiring diagram Power A0650TC Unit Wiring Diagram Control A06 Position Number Typical Designates Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Appendix II. Physical DataGeneral Fan Performance Notes Appendix III. FAN PerformanceTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP 554 Standard Static Option1206 11701165 1225 121550TC**05 Phase Ton Horizontal Supply 765 724Phase Ton Horizontal Supply 974 1067 822 927 1018872 973 1061 923 1019Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentAppendix IV. Electrical Data FLA Appendix IV. Electrical DataMCA/MOCP Determination no C.O. or Unpwrd C.O 78/89 MCA/MOCP Determination no C.O. or Unpwrd C.O.152 159 Wiring Diagrams Appendix V. Wiring Diagram List50TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM START-UP Checklist Pressures Cooling ModeRemove and Store in Job File

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.