Carrier 50TCA04-A07 appendix Space Temperature Sensor Wiring, Temp Resistance

Page 25

Table 5 – Thermistor Resistance vs Temperature Values for Space Temperature Sensor, Supply Air Temperature Sensor, and Outdoor Air Temperature Sensor

TEMP

TEMP

RESISTANCE

(C)

(F)

(Ohms)

 

 

 

--- 40

--- 40

335,651

 

 

 

--- 35

--- 31

242,195

 

 

 

--- 30

--- 22

176,683

 

 

 

--- 25

--- 13

130,243

--- 20

--- 4

96,974

 

 

 

--- 15

5

72,895

 

 

 

--- 10

14

55,298

--- 5

23

42,315

 

 

 

0

32

32,651

 

 

 

5

41

25,395

10

50

19,903

 

 

 

15

59

15,714

 

 

 

20

68

12,494

 

 

 

25

77

10,000

 

 

 

30

86

8,056

35

95

6,530

 

 

 

40

104

5,325

 

 

 

45

113

4,367

50

122

3,601

 

 

 

55

131

2,985

 

 

 

60

140

2,487

65

149

2,082

 

 

 

70

158

1,752

 

 

 

NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.

Outdoor Air Temperature (OAT) Sensor — The OAT is factory-mounted in the Economizer 2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. See Table 5 for temperature-resistance characteristic.

Economizer 2 — The PremierLink control is used with Economizer 2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; Economizer 2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Refer to Table 6 for accessory part numbers

Field connections — Field connections for accessory sensor and input devices are made at the 16-pole terminal block (TB1) located on the control box bottom shelf in front of the PremierLink control. Some input devices also require a 24-vac signal source; connect at LCTB terminal R at “THERMOSTAT” connection strip for this signal source. See connections figures on following pages for field connection locations (and for continued connections at the PremierLink board inputs).

Table 7 provides a summary of field connections for units equipped with Space Sensor. Table 8 provides a summary of field connections for units equipped with Space Thermostat.

Space Sensors - The PremierLink controller is

 

factory-shipped configured for Space Sensor Mode. A

50TC

Carrier T-55 or T-56 space sensor must be used. T-55

space temperature sensor provides a signal of space

 

temperature to the PremierLink control. T-56 provides

 

same space temperature signal plus it allows for

 

 

adjustment of space temperature setpoints from the face of

 

the sensor by the occupants. See Table 5 for temperature

 

versus resistance characteristic on the space sensors.

 

Connect T-55 - See Fig. 36 for typical T-55 internal

 

connections. Connect the T-55 SEN terminals to TB1

 

terminals 1 and 3 (see Fig. 37).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

C08201

Fig. 36 - T-55 Space Temperature Sensor Wiring

TB1PL

SEN 1 J6-7

SEN 3 J6-6

C08212

Fig. 37 - PremierLink T55 Sensor

25

Image 25
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralSupply Fan Belt-Drive Supply FAN Blower SectionSupply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Two-Row Coils Cleaning Condenser CoilPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Refrigerant ChargeCoreMax Access Port Assembly To Use Cooling Charging ChartsCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisSmoke Detectors Convenience OutletsController SystemSensor Smoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor and Controller Tests Sensor Alarm TestDirty Controller Test Dirty Sensor TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningCleaning the Smoke Detector Changing the Dirt Sensor TestAlarm State IndicatorsDetector Indicators Control or Indicator DescriptionProtective Devices TroubleshootingRelief Device Electric HeatersControl Circuit Condenser Fan Motor ProtectionTypical Single Point Installation Completing Heater InstallationPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic Temp Resistance 55 Space Temperature Sensor WiringPremierLink Sensor Usage Temperature Enthalpy SensorOutdoor AIR Return AIR Thermostat Mode Space Sensor ModeField Connection Input Signal TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Tions Indoor CO2 Sensor 33ZCSENCO2 ConnecRecommended Cables CCN BUS Wire CCN Plug PIN Color NumberColor Code Recommendations ManufacturerPremierLink CCN Bus Connections Economizer SystemsRUN Inputs OutputsEconoMi$er Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Enthalpy Changeover SetpointsMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor ConfigurationEconoMi$er IV Sensor Usage EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustDifferential Enthalpy Single EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsPRE-START-UP START-UP, Premierlink Controls START-UP, GeneralPerform System Check-Out Memory ResetInitial Operation and Test Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Number Stages Economizer Available Cooling StagesOAT ≤ SPT 50TC 50TC Fastener Torque Values Loadshed Command Gas and Electric Heat UnitsLinkage Modes Torque Values 50TC Typical Unit Wiring diagram Power A0650TC Unit Wiring Diagram Control A06 Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical DesignatesPhysical Data Cooling Tons Appendix II. Physical DataGeneral Fan Performance Notes Appendix III. FAN PerformanceTon Vertical Supply Ton Horizontal SupplyCFM RPM BHP 554 Standard Static Option1165 1225 11701215 120650TC**05 Phase Ton Horizontal Supply 765 724Phase Ton Horizontal Supply 872 973 1061 822 927 1018923 1019 974 1067Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentAppendix IV. Electrical Data FLA Appendix IV. Electrical DataMCA/MOCP Determination no C.O. or Unpwrd C.O 78/89 MCA/MOCP Determination no C.O. or Unpwrd C.O.152 159 Wiring Diagrams Appendix V. Wiring Diagram List50TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM Pressures Cooling Mode START-UP ChecklistRemove and Store in Job File

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.