Carrier 50TCA04-A07 appendix Outside and Return Air Enthalpy Sensor Wiring

Page 29

The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Differential Enthalpy Control — Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.

Return Air Enthalpy Sensor — Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). See Fig. 42.

levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 43 for typical CO2 sensor wiring schematic.

ENTHALPY CONTROLLER

RED

 

S (OUTDOOR

 

 

 

 

 

+

AIR

 

 

 

 

BRN

 

 

B C

TR

TR1

BLK

ENTHALPY

A

 

 

SENSOR)

 

D

SO

+

 

RED

 

 

 

 

SR

+

 

 

S (RETURN AIR

 

 

 

 

 

 

+

ENTHALPY

 

 

2

3

 

 

 

SENSOR)

 

 

1

 

GRAY/ORN

 

 

 

 

 

 

 

 

 

LED

 

 

 

 

WIRE HARNESS

 

 

 

 

GRAY/RED

IN UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Remove factory-installed jumper across SR and + before connecting wires from return air sensor.

2.Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.

3.Remove sensor mounted on back of control and locate in outside air- stream.

C06019

H G 24 VAC OR

+ - 24 VDC

50TC

+ 0-10VDC

- SIG COM (J4-6) + 4-20mA (J4-5)

NC }ALARM

COM RELAY

NO CONTACTS

2 1 8 7 6 5 4 3 2 1

C07134

Fig. 42 - Outside and Return Air Enthalpy Sensor

Wiring

To wire the return air enthalpy sensor, perform the following:

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthal- py controller.

2.At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.

3.Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.

NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.

The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Indoor Air Quality (CO2 sensor) — The indoor air quality sensor accessory monitors space carbon dioxide (CO2)

Fig. 43 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 43. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-7. See Fig. 44.

29

Image 29
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralSupply Fan Belt-Drive Supply FAN Blower SectionSupply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Two-Row Coils Cleaning Condenser CoilPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Refrigerant ChargeCoreMax Access Port Assembly To Use Cooling Charging ChartsCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisSmoke Detectors Convenience OutletsSensor SystemController Smoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor and Controller Tests Sensor Alarm TestDirty Controller Test Dirty Sensor TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningCleaning the Smoke Detector Changing the Dirt Sensor TestAlarm State IndicatorsDetector Indicators Control or Indicator DescriptionProtective Devices TroubleshootingRelief Device Electric HeatersControl Circuit Condenser Fan Motor ProtectionTypical Single Point Installation Completing Heater InstallationPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic Temp Resistance 55 Space Temperature Sensor WiringOutdoor AIR Return AIR Temperature Enthalpy SensorPremierLink Sensor Usage Thermostat Mode Space Sensor ModeField Connection Input Signal TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Tions Indoor CO2 Sensor 33ZCSENCO2 ConnecRecommended Cables CCN BUS Wire CCN Plug PIN Color NumberColor Code Recommendations ManufacturerPremierLink CCN Bus Connections Economizer SystemsRUN Inputs OutputsEconoMi$er Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Enthalpy Changeover SetpointsMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement ThermostatsEconoMi$er IV Sensor Usage CO2 Sensor ConfigurationDemand Control Ventilation DCV EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustDifferential Enthalpy Single EnthalpyPRE-START-UP Wiring DiagramsEconoMi$er IV Troubleshooting Completion START-UP, Premierlink Controls START-UP, GeneralPerform System Check-Out Memory ResetInitial Operation and Test Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Number Stages Economizer Available Cooling StagesOAT ≤ SPT 50TC 50TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsFastener Torque Values Torque Values 50TC Typical Unit Wiring diagram Power A0650TC Unit Wiring Diagram Control A06 Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical DesignatesPhysical Data Cooling Tons Appendix II. Physical DataGeneral Fan Performance Notes Appendix III. FAN PerformanceCFM RPM BHP Ton Horizontal SupplyTon Vertical Supply 554 Standard Static Option1165 1225 11701215 120650TC**05 Phase Ton Horizontal Supply 765 724Phase Ton Horizontal Supply 872 973 1061 822 927 1018923 1019 974 1067Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentAppendix IV. Electrical Data FLA Appendix IV. Electrical DataMCA/MOCP Determination no C.O. or Unpwrd C.O 78/89 MCA/MOCP Determination no C.O. or Unpwrd C.O.152 159 Wiring Diagrams Appendix V. Wiring Diagram List50TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM Remove and Store in Job File START-UP ChecklistPressures Cooling Mode

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.