Carrier 50TCA04-A07 appendix Troubleshooting, Protective Devices

Page 20

50TC

S If a wiring fault between a sensor and the controller, the controller’s Trouble LED turns on but not the sensor’s.

 

Trouble

Alarm

Power

 

Test/reset

 

switch

 

C07298

Fig. 26 - Controller Assembly

NOTE: All troubles are latched by the duct smoke detector. The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state.

Resetting Alarm and Trouble Condition Trips:

Manual reset is required to restore smoke detector systems to Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Check each sensor for Alarm or Trouble status (indicated by LED). Clear the condition that has generated the trip at this sensor. Then reset the sensor by pressing and holding the reset button (on the side) for 2 seconds. Verify that the sensor’s Alarm and Trouble LEDs are now off. At the controller, clear its Alarm or Trouble state by pressing and holding the manual reset button (on the front cover) for 2 seconds. Verify that the controller’s Alarm and Trouble LEDs are now off. Replace all panels.

TROUBLESHOOTING

Controller’s Trouble LED is On

1.Check the Trouble LED on each sensor connected to the controller. If a sensor’s Trouble LED is on, de- termine the cause and make the necessary repairs.

2.Check the wiring between the sensor and the control- ler. If wiring is loose or missing, repair or replace as required.

Controller’s Trouble LED is Flashing

1.One or both of the sensors is 100% dirty.

2.Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section.

Sensor’s Trouble LED is On

1.Check the sensor’s Dirty LED. If it is flashing, the sensor is dirty and must be cleaned.

2.Check the sensor’s cover. If it is loose or missing, se- cure the cover to the sensor housing.

3.Replace sensor assembly.

Sensor’s Power LED is Off

1.Check the controller’s Power LED. If it is off, de- termine why the controller does not have power and make the necessary repairs.

2.Check the wiring between the sensor and the control- ler. If wiring is loose or missing, repair or replace as required.

Controller’s Power LED is Off

1.Make sure the circuit supplying power to the control- ler is operational. If not, make sure JP2 and JP3 are set correctly on the controller before applying power.

2.Verify that power is applied to the controller’s supply input terminals. If power is not present, replace or re- pair wiring as required.

Remote Test/Reset Station’s Trouble LED Does Not flash When Performing a Dirty Test, But the Controller’s Trouble LED Does

1.Verify that the remote test/station is wired as shown in Fig. 23. Repair or replace loose or missing wiring.

2.Configure the sensor dirty test to activate the control- ler’s supervision relay. See “Changing sensor dirty test operation.”

Sensor’s Trouble LED is On, But the Controller’s Trouble LED is OFF

Remove JP1 on the controller.

PROTECTIVE DEVICES

Compressor Protection

Overcurrent

The compressor has internal linebreak motor protection.

Overtemperature

The compressor has an internal protector to protect it against excessively high discharge gas temperatures.

High Pressure Switch

The system is provided with a high pressure switch mounted on the discharge line. The switch is stem-mounted and brazed into the discharge tube. Trip setting is 630 psig +/- 10 psig (4344 +/- 69 kPa) when hot. Reset is automatic at 505 psig (3482 kPa).

Low Pressure Switch

The system is protected against a loss of charge and low evaporator coil loading condition by a low pressure switch located on the suction line near the compressor. The switch is stem-mounted. Trip setting is 54 psig +/- 5 psig (372 +/- 34 kPa). Reset is automatic at 117 +/- 5 psig (807 +/- 34 kPa).

Evaporator Freeze Protection

The system is protected against evaporator coil frosting and low temperature conditions by a temperature switch mounted on the evaporator coil hairpin. Trip setting is 30_F +/- 5_F (-1_C +/- 3_C). Reset is automatic at 45_F (7_C).

Supply (Indoor) Fan Motor Protection

Disconnect and lockout power when servicing fan motor.

The standard supply fan motor is equipped with internal overcurrent and overtemperature protection. Protection devices reset automatically.

20

Image 20
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceSeasonal Maintenance GeneralSupply FAN Blower Section Supply Fan Belt-DriveAdjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Cleaning Condenser Coil Two-Row CoilsRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantEvaporator Coil Refrigerant ChargeTo Use Cooling Charging Charts CoreMax Access Port AssemblyCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Troubleshooting Cooling System CompressorFilter Drier Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConvenience Outlets Smoke DetectorsSensor SystemController Completing Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionSensor and Controller Tests Sensor Alarm Test Controller Alarm TestDirty Controller Test Dirty Sensor TestDetector Cleaning Remote Test/Reset Station Dirty Sensor TestCleaning the Smoke Detector Changing the Dirt Sensor TestIndicators Alarm StateDetector Indicators Control or Indicator DescriptionTroubleshooting Protective DevicesElectric Heaters Relief DeviceControl Circuit Condenser Fan Motor ProtectionCompleting Heater Installation Typical Single Point InstallationPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Temp ResistanceOutdoor AIR Return AIR Temperature Enthalpy SensorPremierLink Sensor Usage Space Sensor Mode Thermostat ModeField Connection Input Signal TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Indoor CO2 Sensor 33ZCSENCO2 Connec TionsCCN BUS Wire CCN Plug PIN Color Number Recommended CablesColor Code Recommendations ManufacturerEconomizer Systems PremierLink CCN Bus ConnectionsInputs Outputs RUNSupply Air Temperature SAT Sensor EconoMi$erOutdoor Air Lockout Sensor EconoMi$er IV Control ModesDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverEnthalpy Changeover Setpoints Indoor Air Quality IAQ Sensor InputExhaust Setpoint Adjustment Minimum Position ControlDamper Movement ThermostatsEconoMi$er IV Sensor Usage CO2 Sensor ConfigurationDemand Control Ventilation DCV DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV PreparationDifferential Enthalpy Single EnthalpyPRE-START-UP Wiring DiagramsEconoMi$er IV Troubleshooting Completion START-UP, General START-UP, Premierlink ControlsMemory Reset Perform System Check-OutInitial Operation and Test Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Available Cooling Stages Number Stages EconomizerOAT ≤ SPT 50TC 50TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsFastener Torque Values 50TC Typical Unit Wiring diagram Power A06 Torque Values50TC Unit Wiring Diagram Control A06 Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number Typical DesignatesAppendix II. Physical Data Physical Data Cooling TonsAppendix III. FAN Performance General Fan Performance NotesCFM RPM BHP Ton Horizontal SupplyTon Vertical Supply Standard Static Option 5541170 1165 12251215 120650TC**05 Phase Ton Horizontal Supply 724 765Phase Ton Horizontal Supply 822 927 1018 872 973 1061923 1019 974 1067Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data Appendix IV. Electrical Data FLAMCA/MOCP Determination no C.O. or Unpwrd C.O MCA/MOCP Determination no C.O. or Unpwrd C.O. 78/89152 159 Appendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 50TC*A04 Outdoor CircuitingAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM Remove and Store in Job File START-UP ChecklistPressures Cooling Mode

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.