Carrier 50TCA04-A07 appendix Inputs Outputs, Run

Page 33

500 OHM RESISTOR

NOTE 1

RUN

NOTE 3

50HJ540573

ACTUATOR ASSEMBLY

DIRECT DRIVE

ACTUATOR

 

 

BLACK

4

TRANSFORMER

 

 

 

 

 

 

 

GROUND

 

 

 

3

 

 

 

 

5

 

 

 

BLUE

2

 

 

 

 

 

 

 

 

8

 

VIOLET

 

 

6

 

 

 

 

 

PINK

 

 

7

 

 

 

 

 

OAT SENSOR

 

RED

1

24 VAC

 

 

 

 

 

 

 

 

10

 

 

YELLOW

 

11

 

 

 

9

 

 

 

 

 

 

 

WHITE

 

4-20 mA

4-20mA SIGNAL

 

12

TO J9 ON

 

 

 

 

 

PremierLink

 

 

 

 

 

 

 

 

BOARD

 

 

ECONOMISER2 PLUG

50TC

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen sor or HH57A077 enthalpy sensor.

3.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C08310

Fig. 55 - EconoMi$er2 with 4 to 20 mA Control Wiring

Table 11 – EconoMi$er IV Input/Output Logic

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

 

 

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return

 

 

1

2

Damper

 

 

 

 

 

 

High

 

On

On

On

On

 

 

 

Low

On

Off

On

Off

Minimum position

Closed

 

(Free Cooling LED Off)

Below set

 

Off

Off

Off

Off

 

 

 

 

 

 

(DCV LED Off)

Low

 

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

High

On

Off

Off

Off

position and full-open)

closed and full-open)

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

Minimum position

Closed

 

 

 

 

High

 

On

On

On

On

Modulating†† (between min.

Modulating†† (between

 

Low

On

Off

On

Off

position and DCV

closed and DCV

 

(Free Cooling LED Off)

 

 

 

 

 

 

maximum)

maximum)

Above set

 

Off

Off

Off

Off

 

 

(DCV LED On)

 

 

 

 

 

 

 

 

Low

 

On

On

On

Off

 

 

 

High

On

Off

Off

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). ** Modulation is based on the supply-air sensor signal.

†† Modulation is based on the DCV signal.

*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).

††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).

33

Image 33
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralSupply Fan Belt-Drive Supply FAN Blower SectionSupply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Two-Row Coils Cleaning Condenser CoilPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Refrigerant ChargeCoreMax Access Port Assembly To Use Cooling Charging ChartsCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisSmoke Detectors Convenience OutletsSystem ControllerSensor Smoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor and Controller Tests Sensor Alarm TestDirty Controller Test Dirty Sensor TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningCleaning the Smoke Detector Changing the Dirt Sensor TestAlarm State IndicatorsDetector Indicators Control or Indicator DescriptionProtective Devices TroubleshootingRelief Device Electric HeatersControl Circuit Condenser Fan Motor ProtectionTypical Single Point Installation Completing Heater InstallationPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic Temp Resistance 55 Space Temperature Sensor WiringTemperature Enthalpy Sensor PremierLink Sensor UsageOutdoor AIR Return AIR Thermostat Mode Space Sensor ModeField Connection Input Signal TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Tions Indoor CO2 Sensor 33ZCSENCO2 ConnecRecommended Cables CCN BUS Wire CCN Plug PIN Color NumberColor Code Recommendations ManufacturerPremierLink CCN Bus Connections Economizer SystemsRUN Inputs OutputsEconoMi$er Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Enthalpy Changeover SetpointsMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement ThermostatsCO2 Sensor Configuration Demand Control Ventilation DCVEconoMi$er IV Sensor Usage EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustDifferential Enthalpy Single EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionPRE-START-UP START-UP, Premierlink Controls START-UP, GeneralPerform System Check-Out Memory ResetInitial Operation and Test Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Number Stages Economizer Available Cooling StagesOAT ≤ SPT 50TC 50TC Loadshed Command Gas and Electric Heat Units Fastener Torque ValuesLinkage Modes Torque Values 50TC Typical Unit Wiring diagram Power A0650TC Unit Wiring Diagram Control A06 Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position Number Typical DesignatesPhysical Data Cooling Tons Appendix II. Physical DataGeneral Fan Performance Notes Appendix III. FAN PerformanceTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP 554 Standard Static Option1165 1225 11701215 120650TC**05 Phase Ton Horizontal Supply 765 724Phase Ton Horizontal Supply 872 973 1061 822 927 1018923 1019 974 1067Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentAppendix IV. Electrical Data FLA Appendix IV. Electrical DataMCA/MOCP Determination no C.O. or Unpwrd C.O 78/89 MCA/MOCP Determination no C.O. or Unpwrd C.O.152 159 Wiring Diagrams Appendix V. Wiring Diagram List50TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM START-UP Checklist Pressures Cooling ModeRemove and Store in Job File

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.