Carrier 50TCA04-A07 appendix Two-Row Coils, Cleaning Condenser Coil

Page 6

Two-Row Coils

Clean coil as follows:

1.Turn off unit power, tag disconnect.

2.Remove top panel screws on condenser end of unit.

3.Remove condenser coil corner post. See Fig. 8. To hold top panel open, place coil corner post between top panel and center post. See Fig. 9.

50TC

C08205

Fig. 8 - Cleaning Condenser Coil

C08206

Fig. 9 - Propping Up Top Panel

4.Remove screws securing coil to compressor plate and compressor access panel.

5.Remove fastener holding coil sections together at re- turn end of condenser coil. Carefully separate the out- er coil section 3 to 4 in. from the inner coil section. See Fig. 10.

C08207

Fig. 10 - Separating Coil Sections

6.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

7.Secure inner and outer coil rows together with a field-supplied fastener.

8.Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.

Totaline Environmentally Sound Coil Cleaner Application Equipment

S2-1/2 gallon garden sprayer

S Water rinse with low velocity spray nozzle

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in accelerated corrosion of unit parts.

Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit performance or unit shutdown.

High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop.

Totaline Environmentally Sound Coil Cleaner Application Instructions

1.Proper eye protection such as safety glasses is recom- mended during mixing and application.

2.Remove all surface loaded fibers and dirt with a vacu- um

cleaner as described above.

3.Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.

4.Mix Totaline environmentally sound coil cleaner in a 2-1/2 gallon garden sprayer according to the instruc- tions included with the cleaner. The optimum solution temperature is 100_F.

NOTE: Do NOT USE water in excess of 130_F, as the enzymatic activity will be destroyed.

5.Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.

6

Image 6
Contents Table of Contents Safety ConsiderationsSeasonal Maintenance Unit Arrangement and AccessRoutine Maintenance GeneralSupply FAN Blower Section Supply Fan Belt-DriveAdjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Cleaning Condenser Coil Two-Row CoilsEvaporator Coil Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Refrigerant ChargeTo Use Cooling Charging Charts CoreMax Access Port AssemblyCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Filter Drier Troubleshooting Cooling SystemCompressor Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConvenience Outlets Smoke DetectorsSystem ControllerSensor Completing Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionDirty Controller Test Sensor and Controller Tests Sensor Alarm TestController Alarm Test Dirty Sensor TestCleaning the Smoke Detector Detector CleaningRemote Test/Reset Station Dirty Sensor Test Changing the Dirt Sensor TestDetector Indicators IndicatorsAlarm State Control or Indicator DescriptionTroubleshooting Protective DevicesControl Circuit Electric HeatersRelief Device Condenser Fan Motor ProtectionCompleting Heater Installation Typical Single Point InstallationPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Temp ResistanceTemperature Enthalpy Sensor PremierLink Sensor UsageOutdoor AIR Return AIR Field Connection Input Signal Space Sensor ModeThermostat Mode TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Indoor CO2 Sensor 33ZCSENCO2 Connec TionsColor Code Recommendations CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables ManufacturerEconomizer Systems PremierLink CCN Bus ConnectionsInputs Outputs RUNOutdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er EconoMi$er IV Control ModesDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverEnthalpy Changeover Setpoints Indoor Air Quality IAQ Sensor InputDamper Movement Exhaust Setpoint AdjustmentMinimum Position Control ThermostatsCO2 Sensor Configuration Demand Control Ventilation DCVEconoMi$er IV Sensor Usage Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Single EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionPRE-START-UP START-UP, General START-UP, Premierlink ControlsInitial Operation and Test Memory ResetPerform System Check-Out Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Available Cooling Stages Number Stages EconomizerOAT ≤ SPT 50TC 50TC Loadshed Command Gas and Electric Heat Units Fastener Torque ValuesLinkage Modes 50TC Typical Unit Wiring diagram Power A06 Torque Values50TC Unit Wiring Diagram Control A06 Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number Typical DesignatesAppendix II. Physical Data Physical Data Cooling TonsAppendix III. FAN Performance General Fan Performance NotesTon Horizontal Supply Ton Vertical SupplyCFM RPM BHP Standard Static Option 5541215 11701165 1225 120650TC**05 Phase Ton Horizontal Supply 724 765Phase Ton Horizontal Supply 923 1019 822 927 1018872 973 1061 974 1067Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data Appendix IV. Electrical Data FLAMCA/MOCP Determination no C.O. or Unpwrd C.O MCA/MOCP Determination no C.O. or Unpwrd C.O. 78/89152 159 Appendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 50TC*A04 Outdoor CircuitingAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM START-UP Checklist Pressures Cooling ModeRemove and Store in Job File

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.