Carrier 50TCA04-A07 appendix Demand Control Ventilation DCV, CO2 Sensor Configuration

Page 38

50TC

timeclock function in place of the jumper between TR and N. (See Fig. 52.) When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.

Demand Control Ventilation (DCV)

When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.

Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.

A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 setpoint has not been reached. By the time the CO2 level reaches the setpoint, the damper will be at maximum ventilation and should maintain the setpoint.

In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.

(TO x 100OA ) + (TR x 100RA ) =TM

TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air

TR = Return-Air Temperature

RA = Percent of Return Air

TM = Mixed-Air Temperature

Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 64 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 64 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the

graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 12.)

Use setting 1 or 2 for Carrier equipment. (See Table 12.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

Table 12 – EconoMi$er IV Sensor Usage

 

ECONOMI$ER IV WITH OUTDOOR AIR

APPLICATION

 

DRY BULB SENSOR

 

 

Accessories Required

Outdoor Air

None. The outdoor air dry bulb sensor

Dry Bulb

 

is factory installed.

 

 

 

 

 

 

 

Differential

 

CRTEMPSN002A00*

Dry Bulb

 

 

 

 

 

 

 

Single Enthalpy

 

 

HH57AC078

Differential

 

 

HH57AC078

 

 

 

 

and

Enthalpy

 

 

 

 

 

CRENTDIF004A00*

 

 

CO2 for DCV

 

 

 

 

 

 

Control using a

 

 

33ZCSENCO2

Wall-Mounted

 

 

 

 

 

 

 

 

CO2 Sensor

 

 

 

 

 

 

CO2 for DCV

33ZCSENCO2†

 

O

 

 

Control using a

and

 

 

 

CRCBDIOX005A00††

Duct-Mounted

 

 

R

 

33ZCASPCO2**

 

 

 

CO2 Sensor

 

 

 

 

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.

† 33ZCSENCO2 is an accessory CO2 sensor.

**33ZCASPCO2 is an accessory aspirator box required for duct- mounted applications.

†† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.

3.Use the Up/Down button to select the preset number. (See Table 12.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

38

Image 38
Contents Table of Contents Safety ConsiderationsSeasonal Maintenance Unit Arrangement and AccessRoutine Maintenance GeneralSupply FAN Blower Section Supply Fan Belt-DriveAdjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Cleaning Condenser Coil Two-Row CoilsEvaporator Coil Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Refrigerant ChargeTo Use Cooling Charging Charts CoreMax Access Port AssemblyCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Filter Drier Troubleshooting Cooling SystemCompressor Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConvenience Outlets Smoke DetectorsSensor SystemController Completing Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionDirty Controller Test Sensor and Controller Tests Sensor Alarm TestController Alarm Test Dirty Sensor TestCleaning the Smoke Detector Detector CleaningRemote Test/Reset Station Dirty Sensor Test Changing the Dirt Sensor TestDetector Indicators IndicatorsAlarm State Control or Indicator DescriptionTroubleshooting Protective DevicesControl Circuit Electric HeatersRelief Device Condenser Fan Motor ProtectionCompleting Heater Installation Typical Single Point InstallationPremierlinkt Control PremierLink ControllerPremierLink Wiring Schematic 55 Space Temperature Sensor Wiring Temp ResistanceOutdoor AIR Return AIR Temperature Enthalpy SensorPremierLink Sensor Usage Field Connection Input Signal Space Sensor ModeThermostat Mode TB1 Terminal Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Indoor CO2 Sensor 33ZCSENCO2 Connec TionsColor Code Recommendations CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables ManufacturerEconomizer Systems PremierLink CCN Bus ConnectionsInputs Outputs RUNOutdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er EconoMi$er IV Control ModesDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverEnthalpy Changeover Setpoints Indoor Air Quality IAQ Sensor InputDamper Movement Exhaust Setpoint AdjustmentMinimum Position Control ThermostatsEconoMi$er IV Sensor Usage CO2 Sensor ConfigurationDemand Control Ventilation DCV Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Single EnthalpyPRE-START-UP Wiring DiagramsEconoMi$er IV Troubleshooting Completion START-UP, General START-UP, Premierlink ControlsInitial Operation and Test Memory ResetPerform System Check-Out Operating Sequence, Base Unit ControlsOperating Sequence, PremierLink Control 50TC Available Cooling Stages Number Stages EconomizerOAT ≤ SPT 50TC 50TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsFastener Torque Values 50TC Typical Unit Wiring diagram Power A06 Torque Values50TC Unit Wiring Diagram Control A06 Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number Typical DesignatesAppendix II. Physical Data Physical Data Cooling TonsAppendix III. FAN Performance General Fan Performance NotesCFM RPM BHP Ton Horizontal SupplyTon Vertical Supply Standard Static Option 5541215 11701165 1225 120650TC**05 Phase Ton Horizontal Supply 724 765Phase Ton Horizontal Supply 923 1019 822 927 1018872 973 1061 974 1067Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data Appendix IV. Electrical Data FLAMCA/MOCP Determination no C.O. or Unpwrd C.O MCA/MOCP Determination no C.O. or Unpwrd C.O. 78/89152 159 Appendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 50TC*A04 Outdoor CircuitingAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM Remove and Store in Job File START-UP ChecklistPressures Cooling Mode

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.