Carrier 50TCA04-A07 appendix Differential Dry Bulb Control, Outdoor Enthalpy Changeover

Page 35

and D. See Fig. 59 for the corresponding temperature changeover values.

Differential Dry Bulb Control

For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 61.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 52.)

C06034

Fig. 58 - EconoMi$er IV Controller Potentiometer

and LED Locations

19

 

 

18

LED ON

 

D

 

17

 

 

 

16

LED OFF

LED ON

C

15

 

 

 

ECONOMI$ERIV

ECONOMI$ERIV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT (FIELD-PROVIDED)

C07085

50TC

mA

14

 

 

 

 

 

 

LED OFF

 

 

LED ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED ON

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

LED OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED OFF

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

45

50

55

60

65

70

75

80

85

90

95

100

 

 

 

 

 

 

 

DEGREES FAHRENHEIT

 

 

 

 

 

 

 

 

C06035

Fig. 59 - Outside Air Temperature Changeover

Setpoints

(cfm)

30

MINUTE

25

 

PER

20

15

FEET

10

CUBICIN

0

 

5

FLOW

0.13

0.20

0.22

0.25

0.30

0.35

0.40

0.45

0.50

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

C06031

Fig. 60 - Outdoor-Air Damper Leakage

Fig. 61 - Return Air Temperature or Enthalpy Sensor

Mounting Location

In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. (See Fig. 58.)

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See 56.) When the outdoor air enthalpy rises above the outdoor enthalpy changeover setpoint, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. The setpoints are A, B, C, and D. (See Fig. 62.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. (See Fig. 52 and 63.)

35

Image 35
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessRoutine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionSupply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Two-Row Coils Cleaning Condenser CoilRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Evaporator CoilCoreMax Access Port Assembly To Use Cooling Charging ChartsCooling Charging Charts Cooling Charging ChartsCooling Charging Charts Condenser-Fan Location Troubleshooting Cooling SystemCompressor Filter DrierProblem Cause Remedy Cooling Service AnalysisSmoke Detectors Convenience OutletsSensor SystemController Smoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseDirty Sensor Test Sensor and Controller Tests Sensor Alarm TestController Alarm Test Dirty Controller TestChanging the Dirt Sensor Test Detector CleaningRemote Test/Reset Station Dirty Sensor Test Cleaning the Smoke DetectorControl or Indicator Description IndicatorsAlarm State Detector IndicatorsProtective Devices TroubleshootingCondenser Fan Motor Protection Electric HeatersRelief Device Control CircuitTypical Single Point Installation Completing Heater InstallationPremierLink Controller Premierlinkt ControlPremierLink Wiring Schematic Temp Resistance 55 Space Temperature Sensor WiringOutdoor AIR Return AIR Temperature Enthalpy SensorPremierLink Sensor Usage TB1 Terminal Field Connection Input Signal Space Sensor ModeThermostat Mode Field Connection Input SignalLctb Outside and Return Air Enthalpy Sensor Wiring Tions Indoor CO2 Sensor 33ZCSENCO2 ConnecManufacturer CCN BUS Wire CCN Plug PIN Color NumberRecommended Cables Color Code RecommendationsPremierLink CCN Bus Connections Economizer SystemsRUN Inputs OutputsEconoMi$er IV Control Modes Supply Air Temperature SAT SensorEconoMi$er Outdoor Air Lockout SensorOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Enthalpy Changeover SetpointsThermostats Exhaust Setpoint AdjustmentMinimum Position Control Damper MovementEconoMi$er IV Sensor Usage CO2 Sensor ConfigurationDemand Control Ventilation DCV Single Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyPRE-START-UP Wiring DiagramsEconoMi$er IV Troubleshooting Completion START-UP, Premierlink Controls START-UP, GeneralOperating Sequence, Base Unit Controls Memory ResetPerform System Check-Out Initial Operation and TestOperating Sequence, PremierLink Control 50TC Number Stages Economizer Available Cooling StagesOAT ≤ SPT 50TC 50TC Linkage Modes Loadshed Command Gas and Electric Heat UnitsFastener Torque Values Torque Values 50TC Typical Unit Wiring diagram Power A0650TC Unit Wiring Diagram Control A06 Position Number Typical Designates Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Appendix II. Physical DataGeneral Fan Performance Notes Appendix III. FAN PerformanceCFM RPM BHP Ton Horizontal SupplyTon Vertical Supply 554 Standard Static Option1206 11701165 1225 121550TC**05 Phase Ton Horizontal Supply 765 724Phase Ton Horizontal Supply 974 1067 822 927 1018872 973 1061 923 1019Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentAppendix IV. Electrical Data FLA Appendix IV. Electrical DataMCA/MOCP Determination no C.O. or Unpwrd C.O 78/89 MCA/MOCP Determination no C.O. or Unpwrd C.O.152 159 Wiring Diagrams Appendix V. Wiring Diagram List50TC*A04 Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsAppendix VI. cont Motormaster Sensor Locations Catalog No 50TC---1SM Remove and Store in Job File START-UP ChecklistPressures Cooling Mode

50TCA04-A07 specifications

The Carrier 50TCA04-A07 is a prominent model from Carrier, a leader in the heating, ventilation, and air conditioning (HVAC) industry. Designed for commercial applications, this unit exemplifies advanced technology and reliability, catering to a wide array of cooling needs.

One of the most notable features of the Carrier 50TCA04-A07 is its high efficiency. With a cooling capacity that suits various settings, it is engineered to provide excellent performance with minimal energy consumption. The unit achieves impressive Seasonal Energy Efficiency Ratio (SEER) ratings, which not only reduce operational costs but also lower the environmental impact.

The Carrier 50TCA04-A07 employs state-of-the-art inverter technology. This innovation allows the compressor to operate at varying speeds, adjusting its output according to the cooling demand. Consequently, the system can maintain optimal comfort levels while using less energy. Additionally, the inverter technology contributes to quieter operation, making it a suitable choice for environments where noise is a concern.

Durability is a hallmark of the Carrier 50TCA04-A07. Constructed with robust materials, this model is designed to withstand harsh conditions and ensure long-term reliability. The unit is equipped with corrosion-resistant components, extending its lifespan and maintaining performance quality over time.

Another significant characteristic of the Carrier 50TCA04-A07 is its advanced control system. The integrated control panel provides easy access to performance settings and monitoring capabilities. Users can effortlessly adjust temperatures and modes, ensuring a customizable climate. Furthermore, compatibility with smart building management systems enhances operational efficiency and real-time monitoring.

Regarding safety features, the Carrier 50TCA04-A07 is equipped with multiple sensors and automated responses to prevent overheating and ensure safe operation. These safety mechanisms not only protect the unit but also contribute to the overall safety of the installation environment.

In summary, the Carrier 50TCA04-A07 is a highly efficient, durable, and technologically advanced HVAC solution for commercial spaces. Its innovative features, including inverter technology, robust construction, and smart control systems, set it apart in the market, making it a reliable choice for businesses seeking to optimize their climate control needs while minimizing energy consumption and operational costs.