The following diagram illustrates the conversion characteristic:

The conversion values are given by the formula: Raw digital value:=4095 * Ix/20

Ix: Input current value (mA)

According to the formula, a 4mA input is converted to: Raw digital value=4095*4/20 = 819

This is the value setting for SSL.

A 20mA input is converted to a raw reading of 4095. This is the value setting for SSH.

SCOM-100 physical scale values are limited to integer values between -100,000 and 100,000. It is reasonable to select the physical scale in the range of 0 to 10,000 mBar to gain a better resolution.

The configuration command would then be:

Image 38
Contents Page Disclaimer Contents Page Page Device overview ConnectionsLED indications Wiring Power supplyDigital inputs Digital outputs AC1Analog inputs Analog inputVin SCOM-100, User guide Analog input I/O expansion power supply SCOM-100, User guide GSM antenna MicrophonePreparing a SIM card Installing the SIM cardGetting started First power up & factory settings Naming the unit SMS commandsDevice operation XXXX,A..A,..,..,Z..ZConfiguring a digital input for alarming 1100,m,n,s,a,d1100,0,1,Door contact,3,30 My SCOM-100 Door contact1101,m,n,ID1,ID2 Setting alarm message’s texts0630,ID,s My SCOM-100 Door contact Door is opened 0630,1,Door is opened 0630,2,Door is closed0630,1,Door is opened 0630,2,Door is closed 1101,0,1,2,1 My SCOM-1001110,m,n Clearing the digital input configurationDoor contact Door is closed 1000,m,n Setting a digital outputControlling the digital outputs 1000,0,21071,m,n Configuring an output as a closed contact1001,0,2 1071,0,21070,m,n Pulse digital output1010,0,2,25 Setting a digital output after a delay1010,m,n,s Resetting a digital output after a delay 1020,m,n,h,mn1021,m,n,h,mn Digital output time based scheduling 1040,m,n,mon,moffTime schedule program 1700,ID,d,P1B-P1D,P2B-P2D,…,P8B-P8D1701,ID,P 1700,1,0,800-120,1130-1001645-1801030,m,n,ID 1090,m,n,ID Clearing the digital output configuration1701,3,50 1200,m,n,s,SSL,SSH,SCL,SCH,ALL,ALH,u,d Analog signal alarmingAnalog input configuration ALH SCOM-100, User guide 1201,m,n,ID1,ID2 Setting alarm message’s texts for analog inputs1200,0,2,Pressure,819,4095,0,10000,2500 8500,mBar,15 1210,m,n Clearing the analog input configurationSetting the analog inputs alarm deadband 1800,d1250,id,m,n,m1,n1,sp,g,it,dt,ct,h Special I/O Functions1 ON/OFF and PID control 1255,id,sp 1251,id,s1260,id 1252,id,m,n1253,id 0500,id,n,p,c1,c2,c3 User administrationCreate a new user Set a DI alarm recipient Change user configurationDefining specific alarm recipients Delete a userClear AI alarm recipients Set an AI alarm recipientClear DI alarm recipients RUN Control command Device status & mode controlsSetting the device status Monitor command1105,m,n,v Controlling the device statusControlling the device response Send acknowledgement SMSResponse format Setting up an SMS counterMerge concurrent alarms Setting date and time Setting a GSM PIN5100 Monitoring commandsMonitoring capabilities UNITMy SCOM-100Connecting a PC Using the Hyperterminal for configurationSCOM-100, User guide SCOM-100, User guide Atsms=1100,0,1,Door contact,3,30 Using the Scom Configurator for configurationAte1 Using the microphone input Appendix Command referenceGeneral parameter settings SMS User configuration Output control & configuration Input configuration 5 I/O Functions RTC & Time scheduling Monitoring commands AI/DI/AO/DO Troubleshooting Page Technical specifications Main unitGE-DIO-42 Digital I/O Expansion module Error handling Status LED indications LEDDefault parameter values Factory settings GE-DIO-42 Digital I/O expansionSetting an I/O expansion module address Dip switch settings Module number m RS232C connector layout PIN