ALH:

Alarm high limit in physical units

 

(number in the range of SCL to SCH

 

with one optional decimal digit.

 

Example: ALH = 121.5)

u:

Physical unit (0-15 characters)

d:

Delay time in seconds (0-65535)

For example let us explain all the different parameter settings to use a 4-20mA, 0-10 bar pressure sensor wired on analog input 2 on the main unit (See section 2.4.2).

The pressure sensor characteristic is shown in the diagram below:

The 4-20mA input signal is converted by the internal A/D converter in the digital raw range of 819 to 4095.

Image 37
Contents Page Disclaimer Contents Page Page Connections Device overviewLED indications Power supply WiringDigital inputs AC1 Digital outputsAnalog input Analog inputsVin SCOM-100, User guide Analog input I/O expansion power supply SCOM-100, User guide Microphone GSM antennaGetting started Installing the SIM cardPreparing a SIM card First power up & factory settings Device operation SMS commandsNaming the unit XXXX,A..A,..,..,Z..Z1100,m,n,s,a,d Configuring a digital input for alarmingMy SCOM-100 Door contact 1100,0,1,Door contact,3,300630,ID,s Setting alarm message’s texts1101,m,n,ID1,ID2 0630,1,Door is opened 0630,2,Door is closed 1101,0,1,2,1 0630,1,Door is opened 0630,2,Door is closedMy SCOM-100 Door contact Door is opened My SCOM-100Door contact Door is closed Clearing the digital input configuration1110,m,n Controlling the digital outputs Setting a digital output1000,m,n 1000,0,21001,0,2 Configuring an output as a closed contact1071,m,n 1071,0,2Pulse digital output 1070,m,n1010,m,n,s Setting a digital output after a delay1010,0,2,25 1020,m,n,h,mn Resetting a digital output after a delay1021,m,n,h,mn 1040,m,n,mon,moff Digital output time based scheduling1700,ID,d,P1B-P1D,P2B-P2D,…,P8B-P8D Time schedule program1030,m,n,ID 1700,1,0,800-120,1130-1001645-1801701,ID,P 1701,3,50 Clearing the digital output configuration1090,m,n,ID Analog input configuration Analog signal alarming1200,m,n,s,SSL,SSH,SCL,SCH,ALL,ALH,u,d ALH SCOM-100, User guide 1200,0,2,Pressure,819,4095,0,10000,2500 8500,mBar,15 Setting alarm message’s texts for analog inputs1201,m,n,ID1,ID2 Setting the analog inputs alarm deadband Clearing the analog input configuration1210,m,n 1800,d1 ON/OFF and PID control Special I/O Functions1250,id,m,n,m1,n1,sp,g,it,dt,ct,h 1251,id,s 1255,id,sp1253,id 1252,id,m,n1260,id Create a new user User administration0500,id,n,p,c1,c2,c3 Defining specific alarm recipients Change user configurationSet a DI alarm recipient Delete a userClear DI alarm recipients Set an AI alarm recipientClear AI alarm recipients Setting the device status Device status & mode controlsRUN Control command Monitor commandControlling the device response Controlling the device status1105,m,n,v Send acknowledgement SMSMerge concurrent alarms Setting up an SMS counterResponse format Setting a GSM PIN Setting date and timeMonitoring capabilities Monitoring commands5100 UNITMy SCOM-100Using the Hyperterminal for configuration Connecting a PCSCOM-100, User guide SCOM-100, User guide Ate1 Using the Scom Configurator for configurationAtsms=1100,0,1,Door contact,3,30 Using the microphone input General parameter settings Command referenceAppendix SMS User configuration Output control & configuration Input configuration 5 I/O Functions RTC & Time scheduling Monitoring commands AI/DI/AO/DO Troubleshooting Page Main unit Technical specificationsGE-DIO-42 Digital I/O Expansion module Error handling LED Status LED indicationsGE-DIO-42 Digital I/O expansion Default parameter values Factory settingsSetting an I/O expansion module address Dip switch settings Module number m PIN RS232C connector layout