| 39 |
1200,0,2,Pressure,819,4095,0,10000,2500,
8500,mBar,15
The low alarm limit is set to 2.5 Bar, the high alarm limit to 9.5 Bar. A 15 second delay is also set so that the input signal must persist in value and exceed alarm limits (low or high) for 15 seconds. If these clauses are met then an alarm SMS will be initiated.
Note: Alarm annunciation is cancelled if the respective Scale (low or high) and limit alarm values (low or high) are equal.
4.5.2 Setting alarm message’s texts for analog inputs
A similar command to the one for digital inputs is available to associate low and high alarm events with respective SMS messages
The configuration command is:
1201,m,n,ID1,ID2
1201: | Command ID |
m: | Module number (0 for |
| unit, |
n: | Input number |
| unit, |
ID1: | ID number |
| for exceeding the low limit |
ID2: | ID number |
| for exceeding the high limit |
Note: ID1/ID2 value 0 means no message.