E. EXHAUST REQUIREMENTS

Exhaust duct work should be designed and installed by a qualified professional. Improperly sized duct work will create excessive back pressure which results in slow drying, increased use of energy, and shutdown of the burner by the airflow (sail) switch, burner hi-limit, or lint chamber hi-heat protector thermostat.

Where possible, it is suggested to provide a separate (single) exhaust duct for each dryer.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN CREATE A POTENTIAL FIRE HAZARD.

CAUTION: DRYER MUST BE EXHAUSTED TO THE OUTDOORS.

The exhaust duct work should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns as possible. The shape of the duct work is not critical so long as the minimum cross section area is provided. Single or independent dryer venting is recommended.

It is suggested that the use of 90° turns be avoided; use 30° or 45° angles instead.

The duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the ducts to be added should overlap the duct to which it is connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Additionally, inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and cleaning.

IMPORTANT: When connecting duct work to the dryer exhaust duct, be sure that when screws are used they do not restrict the operation (both opening and closing) of the damper.

NOTE: When the exhaust duct passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches (5 cm) larger (all the way around) than the duct. The duct must be centered within this opening.

To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward should be installed where the exhaust exits the building. If the duct work travels vertically up through the roof, it should be protected from the weather by using a 180° turn to point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and the nearest obstruction (i.e., roof or ground level).

IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct work.

IMPORTANT: Exhaust back pressure measured by a manometer at the dryer exhaust duct area must not exceed 0.3 inches of water column (0.75 mbar).

12

Image 16
Contents EURO-24 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Routine Maintenance Section Important InformationSafety Precautions Personal Injury or Fire could ResultStandards Specifications SpecificationsSpecifications Installation Procedures UNPACKING/SETTING UPLocation Requirements Dryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Important Venting Reminders Electrical Information Must be Provided Black White Green Neutral Important a Circuit Serving Each Dryer Must be Provided Important a Circuit Serving Each Dryer Must be Provided Electrical Service Specifications PER Dryer EURO-24 GAS EURO-24 SteamGAS Information Injury and Improper Operation of the Dryer26.1 mb 14.92 29.9 mbPage Page Steam Information 862 KPaPage Compressed AIR Supply AIR Pressure Page Steam Damper Air Piston Flow Control Operation Adjustment Preparation for OPERATION/START-UP Preoperational Tests GAS Models onlyPreoperational Instructions Basket CoatingPage OPL Models Shut Down Instructions Service SERVICE/PARTS InformationParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Routine Maintenance CleaningAdjustments LubricationLint Drawer Removal No L.E.D. light emitting diode display TroubleshootingDrive motor not operating does not start Blower motor not operating does not start Microprocessor computer display reads dSFL Microprocessor controller computer display reads doorPage Failed oven contactor/relay Failed heat selector switch Dryer operates but is taking too long to dry Condensation on main door glassScraping noise from basket tumbler area Excessive noise and/or vibrationDrive motor only not operating Heating unit not operating ALL temperature selectionsBlower motor only not operating Heat unit not operating for only one 1 temperature selection Dryer operates but is taking too long to dry loadSail switch is fluttering for GAS and Electric Models only Technical Information Data LabelData Label Reversing Timer SPIN/DWELL Adjustments Timing LegendProcedure for Functional Check Replacement Components Page ADC 08/03/99-25 01/18/00-25 07/14/00-20