E. EXHAUST REQUIREMENTS

Exhaust duct work should be designed and installed by a qualified professional. Improperly sized duct work will create excessive back pressure which results in slow drying, increased use of energy, and shutdown of the burner by the airflow (sail) switch, burner hi-limit, or lint chamber hi-heat protector thermostat.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN CREATE A POTENTIAL FIRE HAZARD.

CAUTION: DRYER MUST BE EXHAUSTED TO THE OUTDOORS.

The exhaust duct work should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns as possible. The shape of the duct work is not critical so long as the minimum cross section area is provided. Single or independent dryer venting is recommended.

It is suggested that the use of 90° turns be avoided; use 30° and/or 45° angles instead.

The duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the ducts to be added should overlap the duct to which it is connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Additionally, inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and cleaning.

IMPORTANT: When connecting duct work to the dryer exhaust duct, be sure that when screws are used they do not restrict the operation (both opening and closing) of the damper.

NOTE: When the exhaust duct passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches larger (all the way around) than the duct. The duct must be centered within this opening.

To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward should be installed where the exhaust exits the building. If the duct work travels vertically up through the roof, it should be protected from the weather by using a 180° turn-to-point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and the nearest obstruction (i.e., roof or ground level).

IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct work.

IMPORTANT: Exhaust back pressure measured by a manometer at the dryer exhaust duct area must not exceed 0.3 inches of water column.

12

Image 16
Contents Super AD-30 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Troubleshooting Section Important InformationSafety Precautions What to do if YOU Smell GASPage Super AD-30 Specifications SpecificationsSpecifications Installation Procedures UNPACKING/SETTING UPLocation Requirements Section DDryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Important Venting Reminders Electrical Information Page Green Phase 3ø Hookup for GAS and Steam Dryers only Page Super ADG-30DS Gas Reversing Super ADS-30DS Steam Reversing GAS Information Piping/Connections Page Page Steam Information Page 70 psi Normal 80 psi90 psi Page Preparation for Operation Preoperational Tests Page Preoperational Instructions Page OPL Models Shut Down Instructions Service SERVICE/PARTS InformationParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Routine Maintenance CleaningAdjustments LubricationNo L.E.D. light emitting diode display TroubleshootingDrive motor not operating does not start Blower motor not operating does not start Microprocessor computer display reads dSFL Microprocessor controller computer display reads doorPage No heat for Steam Models only Dryer operates but is taking too long to dryDryer or scraping noise at basket tumbler area Condensation on main door glassExcessive noise and/or vibration Drive motor only not operating Blower motor only not operatingHeating unit not operating ALL temperature selections Heat unit not operating for only one 1 temperature selectionDryer operates but is taking too long to dry load Failed hi-limit thermostat for GAS and Electric Models onlyPage Reversing Timer SPIN/DWELL Adjustments Timing LegendData Label Technical InformationContact American Dryer Corporation Data Label Procedure for Functional Check Replacement Components Microprocessor computer BoardDirect Spark Ignition DSI System