IMPORTANT VENTING REMINDERS

1.Duct work size and installation should be done by a qualified professional.

2.The dryer must be exhausted to the outdoors.

3.Duct work should be routed as short as possible to the outdoors with as few elbows as possible.

4.Avoid 90° turns ... use 30° or 45° turns instead.

5.The size of the duct work must be a minimum of 10-inches if the exhaust length exceeds 10 feet.

6.The inside of the duct work should be as smooth as possible ... with no projections from sheet metal screws.

7.ALL ducts should be taped to prevent moisture and lint from escaping into the building.

8.Inspection/clean out doors should be installed throughout strategic points in the duct work for periodic inspection and cleaning.

9.Wherever the duct passes through combustible materials, the opening must be 2-inches larger (all the way around) than the duct. The duct must be centered within this opening.

10.The outside of the duct work must be protected from the weather. A 90° elbow must be used for horizontal run and when vertically through a roof by using a 180° turn to point the opening downward. Distance between the exhaust duct and the nearest obstruction (i.e., roof or ground) must be twice the diameter of the duct.

11.DO NOT use screens or caps on the outside opening of the exhaust duct work.

12.Exhaust back pressure measured by a manometer at the dryer exhaust duct area must not exceed 0.3 inches of water column.

17

Image 21
Contents Super AD-30 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Troubleshooting Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsPage Specifications Super AD-30 SpecificationsSpecifications UNPACKING/SETTING UP Installation ProceduresSection D Location RequirementsDryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Important Venting Reminders Electrical Information Page Green Phase 3ø Hookup for GAS and Steam Dryers only Page Super ADG-30DS Gas Reversing Super ADS-30DS Steam Reversing GAS Information Piping/Connections Page Page Steam Information Page Normal 80 psi 70 psi90 psi Page Preparation for Operation Preoperational Tests Page Preoperational Instructions Page OPL Models Shut Down Instructions SERVICE/PARTS Information ServiceParts Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Cleaning Routine MaintenanceLubrication AdjustmentsTroubleshooting No L.E.D. light emitting diode displayDrive motor not operating does not start Blower motor not operating does not start Microprocessor controller computer display reads door Microprocessor computer display reads dSFLPage Dryer operates but is taking too long to dry No heat for Steam Models onlyCondensation on main door glass Dryer or scraping noise at basket tumbler areaExcessive noise and/or vibration Blower motor only not operating Drive motor only not operatingHeat unit not operating for only one 1 temperature selection Heating unit not operating ALL temperature selectionsFailed hi-limit thermostat for GAS and Electric Models only Dryer operates but is taking too long to dry loadPage Timing Legend Reversing Timer SPIN/DWELL AdjustmentsTechnical Information Data LabelContact American Dryer Corporation Data Label Microprocessor computer Board Procedure for Functional Check Replacement ComponentsDirect Spark Ignition DSI System