Consistent gas pressure is essential at ALL gas connections. It is recommended that a 3/4-inch pipe gas loop be installed in the supply line serving a bank of dryers. An in-line pressure regulator must be installed in the gas supply line (header) if the (natural) gas pressure exceeds 12.0 inches of water column pressure. Refer to the illustrations on page 25 for details.

NOTE: A water column (W.C.) test pressure of 3.5 inches for natural gas and 10.5 inches for L.P. (liquid propane) dryers is required at the gas valve pressure tap of each dryer for proper and safe operation.

A1/8" N.P.T. plugged tap, accessible for a test gauge connection, must be installed in the main gas supply line immediately upstream of each dryer.

IMPORTANT: Pipe joint compounds that resist the action of natural gas and L.P. gas must be used.

NOTE: Test ALL connections for leaks by brushing on a soapy water solution (liquid detergent works well).

WARNING: NEVER TEST FOR LEAKS WITH A FLAME!!!

ALL components/materials must conform to National Fuel Gas Code specifications,or in CANADA, the Canadian Installation Codes. It is important that gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total amount of ALL the appliance BTU's being supplied.

27

Image 31
Contents Super AD-30 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Troubleshooting Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsPage Specifications Super AD-30 SpecificationsSpecifications UNPACKING/SETTING UP Installation ProceduresSection D Location RequirementsDryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Important Venting Reminders Electrical Information Page Green Phase 3ø Hookup for GAS and Steam Dryers only Page Super ADG-30DS Gas Reversing Super ADS-30DS Steam Reversing GAS Information Piping/Connections Page Page Steam Information Page 70 psi Normal 80 psi90 psi Page Preparation for Operation Preoperational Tests Page Preoperational Instructions Page OPL Models Shut Down Instructions Service SERVICE/PARTS InformationParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Cleaning Routine MaintenanceLubrication AdjustmentsNo L.E.D. light emitting diode display TroubleshootingDrive motor not operating does not start Blower motor not operating does not start Microprocessor controller computer display reads door Microprocessor computer display reads dSFLPage Dryer operates but is taking too long to dry No heat for Steam Models onlyDryer or scraping noise at basket tumbler area Condensation on main door glassExcessive noise and/or vibration Blower motor only not operating Drive motor only not operatingHeat unit not operating for only one 1 temperature selection Heating unit not operating ALL temperature selectionsFailed hi-limit thermostat for GAS and Electric Models only Dryer operates but is taking too long to dry loadPage Timing Legend Reversing Timer SPIN/DWELL AdjustmentsData Label Technical InformationContact American Dryer Corporation Data Label Microprocessor computer Board Procedure for Functional Check Replacement ComponentsDirect Spark Ignition DSI System