American Dryer Corp AD-15 Phase 7 Important Venting Reminders, Electrical Information

Page 10

Illus. C (refer to the previous page) shows the minimum cross section area for multiple dryer venting. These figures must be increased in proportion if the main duct run from the last dryer to where it exhausts has numerous elbows or is unusually long.

IMPORTANT:

!For extended ductwork runs, the cross section area of the duct can only be increased to an extent. For extended ductwork runs, a professional heating, ventilating, and air-conditioning (HVAC) firm should be consulted for proper venting information.

IMPORTANT VENTING REMINDERS

Ductwork size and installation should be done by a qualified professional.

The dryer must be exhausted to the outdoors.

Ductwork should be routed as short as possible to the outdoors with as few elbows as possible.

Avoid 90° turns, use 30° or 45° turns instead.

The size of the ductwork must be a minimum of 8-

inches (20.32 cm) for horizontal runs and 10-inches (25.4 cm) for vertical runs.

The inside of the ductwork should be as smooth

as possible with no projections from sheet metal screws.

Ducts added should overlap the duct to which it is to be connected.

ALL ducts should be taped to prevent moisture and lint from escaping into the building.

Inspection or clean out doors should be installed

throughout strategic points in the ductwork for periodic inspection and cleaning.

Whenever the duct passes through combustible materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

The outside of the ductwork must be protected from the weather. A 90° elbow must be used for horizontal run and when vertically through a roof by using a 180° turn to point the opening downward. The distance between the exhaust duct and the nearest obstruction (i.e., roof or ground) must be twice the diameter of the duct.

DO NOT use screens, louvers, or caps on the outside opening of the exhaust ductwork.

Exhaust back pressure measured by a manometer

at the dryer exhaust duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column (W.C.).

Exhaust ductwork outlets should not be located in an area directly where make-up air openings are located.

WARNING:

!DRYER MUST NEVER BE OPERATED WITHOUT THE LINT FILTER/SCREEN IN PLACE, EVEN IF AN EXTERNAL LINT COLLECTION SYSTEM IS USED.

IMPORTANT:

!It is recommended that exhaust or booster fans not be used in the exhaust ductwork system.

ELECTRICAL INFORMATION

Electrical Requirements

ALL electrical connections must be made by a properly licensed and competent electrician. This is to ensure that the electrical installation is adequate and conforms to local and state regulations or codes. In the absence of such codes, ALL electrical connections, materials, and workmanship must conform to the applicable requirements of the National Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in Canada, the Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.

IMPORTANT:

!Failure to comply with these codes or ordinances, and/or the requirements stipulated in this manual can result in personal injury or component failure.

NOTE:

Component failure due to improper installation will VOID THE WARRANTY.

Each dryer should be connected to an independently protected branch circuit. The dryer must be connected with copper wire only. DO NOT use aluminum wire; it could create a fire hazard. The copper conductor wire/cable must be of proper ampacity and insulation in accordance with electric codes for making ALL service connections.

NOTE:

!The use of aluminum wire will VOID THE WARRANTY.

An individual ground circuit must be provided to each dryer, do not daisy chain.

Component failure due to improper voltage application will VOID THE WARRANTY.

IMPORTANT:

A separate protected circuit must be provided to each dryer.

The dryer must be connected to the electric supply shown on the data label. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

The wire size must be properly sized to handle the related current.

WARNING:

208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

8

American Dryer Corp.

113243-1

Image 10
Contents AD-15 Phase Installation Manual ADC Part NoRetain This Manual In a Safe Place For Future Reference Date of Purchase Model no RESELLER’S Name Serial NumbersTable of Contents What to do if YOU Smell GAS Safety PrecautionsLatest Edition Specifications FIPUNPACKING/SETTING UP Installation ProceduresLocation Requirements Fresh AIR Supply Requirements Dryer Enclosure RequirementsExhaust Requirements Horizontal Venting Single Dryer VentingIllus. a Illus. B Illus. C Vertical VentingMultiple Dryer Common Venting Important Venting Reminders Electrical InformationGas and Steam Models Only GroundingKLWHRU5HG Electrical ConnectionsFor 110V Applications For 208-230/240V Applications GAS Information Gas SupplyNever Test for Leaks with a Flame Steam InformationVoid the Warranty 0LQLPXP6XSSO\ 1RUPDO0DLPXP6XSSO\ Preparation for OPERATION/START-UP GAS and Electric Models the sail switchPreoperational Tests Basket Tumbler Coating GAS and Electric Models only Sail SwitchPreoperational Instructions Reversing Timer SPIN/DWELL Adjustments MIN RemainSERVICE/PARTS Information Warranty InformationCleaning Routine MaintenanceSuggested Cleaning Schedule Data Label Information Procedure for 113243-1 Phase Manual Reset Burner HI-LIMIT InstructionsDual Timer Installation Before YOU Start Check Local Codes and PermitsOptional Manual Bypass NON-COIN CoinF.E. System Diagnostics Messages F.E. System Parts Break DownADC 113243 1 2/03/04