American Dryer Corp AD-15 Phase 7 installation manual Void the Warranty

Page 16

IMPORTANT:

!Coil failure due to improper pH level will VOID THE ARRANTY.

Steam Requirements

&RQVXPSWLRQ+HDW0D[LPXP￿,QSXW￿￿2SHUDWLQJ1RUPDO￿￿$SSUR[LPDWH￿/RDG￿￿6WHDP￿￿￿￿￿￿3UHVVXUHSVLJOEV￿KU￿￿￿￿￿%KS￿￿￿￿￿NJ￿KU￿￿￿N3D

Shaded areas are stated in metric equivalents

*The minimum operating pressure is 100 psig (689.47 kPa) for optimum fresults.

Installation Instructions

To ensure an adequate supply of steam is provided, be sure that the steam supply lines and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam supply lines and steam return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean, dry steam must be provided to the dryer.

IMPORTANT:

!Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

The pressure of the condensate in the steam supply line will cause water hammer and subsequent heat exchanger (steam coil) failure. The steam supply connection into the main supply line must be made with a minimum 10-inch (25.4 cm) riser. This will prevent any condensate from draining towards the dryer.

The steam supply line to the dryer must include a 12-inch (30.48 cm) riser along with a drip trap and check valve. This will prevent any condensate from entering the steam coil.

Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains.

Shutoff valves for each dryer should be installed in the supply line, return line, and drip trap return line. This will allow the dryer to be isolated from the supply main and the return main if the dryer needs maintenance work.

Install an inverted bucket steam trap and check valve at least 12-inches (30.48 cm) below the steam coil as close to the coil as possible. A trap with a capacity of 150 lbs (68 kg) of condensate per hour at 125 psi (8.62 bar) is needed for each unit.

The supply line and the return line should be insulated. This will save energy and provide for the safety of the operator and maintenance personnel.

Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing steam coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch (6.35 mm) for every 1 foot (0.31 meters) back towards the steam supply header causing the condensate in the line to drain to the header. Install a bypass trap in any low point to eliminate wet steam.

IMPORTANT:

!Flexible hoses/couplings must be used. Coil failure due to hard plumbing connections will

VOID THE WARRANTY.

14

American Dryer Corp.

113243-1

Image 16
Contents AD-15 Phase Installation Manual ADC Part NoRetain This Manual In a Safe Place For Future Reference Date of Purchase Model no RESELLER’S Name Serial NumbersTable of Contents What to do if YOU Smell GAS Safety PrecautionsLatest Edition Specifications FIPUNPACKING/SETTING UP Installation ProceduresLocation Requirements Fresh AIR Supply Requirements Dryer Enclosure RequirementsExhaust Requirements Horizontal Venting Single Dryer VentingIllus. a Illus. B Illus. C Vertical VentingMultiple Dryer Common Venting Important Venting Reminders Electrical InformationGas and Steam Models Only GroundingKLWHRU5HG Electrical ConnectionsFor 110V Applications For 208-230/240V Applications GAS Information Gas SupplyNever Test for Leaks with a Flame Steam InformationVoid the Warranty 0LQLPXP6XSSO\ 1RUPDO0DLPXP6XSSO\ Preparation for OPERATION/START-UP GAS and Electric Models the sail switchPreoperational Tests Basket Tumbler Coating GAS and Electric Models only Sail SwitchPreoperational Instructions Reversing Timer SPIN/DWELL Adjustments MIN RemainSERVICE/PARTS Information Warranty InformationCleaning Routine MaintenanceSuggested Cleaning Schedule Data Label Information Procedure for 113243-1 Phase Manual Reset Burner HI-LIMIT InstructionsDual Timer Installation Before YOU Start Check Local Codes and PermitsOptional Manual Bypass NON-COIN CoinF.E. System Diagnostics Messages F.E. System Parts Break DownADC 113243 1 2/03/04