Vector VEC054D owner manual Permanent Installation, Connection To Load, Operating Tips

Page 10

90548011 VEC054D INVERTER.qxp 3/6/09 10:41 AM Page 9

Permanent Installation

The permanent installation of the inverter and the required wiring and safety devices to the 12 Volt DC power source must be performed by a professional installer. Further requirements are:

1.The inverter is supplied with 4 Special Crimp Connectors to connect the power source wiring to the inverter DC input terminals. They are designed to be crimped onto #2AWG copper conductor cables (not supplied).

2.The #2AWG power source cables must not exceed 6 feet in length.

3.A 300 Amp ANL Fuse (not supplied) installed in the proper Fuse Holder (not supplied) must be connected in- line as part of the positive power source input cable as close as possible to the power source connections.

4.A #12AWG insulated wire should be connected between the Grounding Terminal on the inverter (see “Controls and Functions”, “Back View Diagram” on page 4 ) and the ground terminal on the appliance (such as a TV or Radio) to minimize electrical noise and reception interference.

CAUTION: Do not connect this wire to the inverter’s Negative (Black, -) DC input terminals.

CAUTION: Violation of these requirements may result in unsafe operation and/or equipment failure. Damage to the inverter as a result of improper installation voids the warranty.

The DC power source must be a well-regulated DC power supply as typically found in vehicle and deep-cycle marine batteries. The DC power source may also be two 12 volt batteries connected in parallel. On larger applications the power source may be several batteries connected in parallel as shown in the following “Permanent Battery Configuration” diagram.

Permanent Battery Configuration Diagram

 

BATTERY CHARGING

 

FUSE TO BATTERY LENGTH

 

 

+ FUSE TO INVERTER LENGTH

 

FROM COMMERCIAL

 

AC, ENGINE, SOLAR, ETC.

 

 

(MAX FEET OF

 

 

 

 

 

 

 

 

 

 

AWG WIRE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(See the “Specifications” section)

 

 

BATTERY

 

 

FUSE HOLDER

 

 

 

 

 

ANL FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAXX SST™

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER

 

 

 

 

 

 

 

 

 

 

(MAX FEET

OF

 

 

BATTERY

 

 

 

 

 

 

 

 

 

 

AWG WIRE)

 

 

 

 

 

 

 

 

(See the “Specifications” section)

 

 

BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: For typical heavy-duty uses in a Permanent Installation, an ANL fuse must be added as close as possible to the power source (battery) positive terminal. The fuse amperage size must be appropriate to allow simultaneous operation of all the AC appliances to be powered, with delay characteristics that allow for the momentary high start-up current requirements of inductive loads. Use the specified fuse block (fuse holder) and fuse. For full rated output and motor start-up surge output, ensure that the installation is configured to handle the full load. See the “Permanent Installation” section of this Instruction Manual.

Connection To Load

The Power Inverter is equipped with standard North American three-prong type outlets. Plug the cord from the equipment you wish to operate into the AC outlet(s). Make sure the combined load requirement of your equipment does not exceed maximum continuous power.

The Power Inverter is engineered to be connected directly to standard electrical and electronic equipment in the manner described above. Do not connect the Power Inverter to household or RV AC distribution wiring. Do not connect the Power Inverter to any AC load circuit in which the neutral conductor is connected to ground (earth) or to the negative of the DC (battery) source.

WARNING: TO REDUCE THE RISK OF ELECTRIC SHOCK, PROPERTY DAMAGE OR PERSONAL INJURY: Never connect unit directly to AC distribution wiring.

Operating Tips

For best operating results, the inverter should be placed on a stable, flat surface. The inverter should only be used in locations that meet the following criteria:

DRY — Do not allow water or other liquids to come into contact with the inverter.

COOL — Surrounding air temperature should be between –0°C and 40°C — ideally between 15°C and 25°C (60-80°F). Keep the inverter away from direct sunlight, when possible.

9

Image 10 Contents
Maxx Ssttm VEC054DSafety Guidelines / Definitions Volts Minimum Gage for Cord SetsImportant Safety Instructions Important Cable InformationFront View Diagram Back View Diagram FeaturesMaxx SST Features IntroductionAppliance Power Consumption Power Inverter Output WaveformPrinciple of Operation 120VAC Appliance Consumption in Amps and Watts ChartAppliance AMPS@ WATTS@ 880Operating Instructions Power Source RequirementsDetermining Battery Size RuntimeInstallation Protective FeaturesBattery Operating Times Temporary Installation Installation ProceduresOperating Environment Connection To Load Permanent Installation#2AWG power source cables must not exceed 6 feet in length Operating TipsCommon Audio/Visual Problems TroubleshootingProblem Solution Care and Maintenance Fault Protection and Troubleshooting GuideResetting the Unit Fuse Replacement Preventive MaintenanceAccessories SpecificationsYear Limited Warranty Program Compact DE 2000 W Lignes Directrices EN Matière DE SÉCURITÉ/DÉFINITIONS Directives DE Sécurité Importantes Avertissement Pour Réduire LE Risque D’INCENDIERenseignements Importants SUR LE Câble Conserver CES DirectivesCaractéristiques Avertissement Pour Réduire LE Risque DE BlessuresPrincipe DE Fonctionnement Commandes et fonctionsCaractéristiques du Maxx SST Forme d’onde de sortie du convertisseur continu-alternatifConsommation Énergétique DES Appareils Électriques Produits incompatiblesPuissance À Appareil120 V C.A Détermination de la taille de la batterie FonctionnementExigences relatives à la source d’alimentation Durée de fonctionnementCaractéristiques de sécurité Durées de fonctionnement des batteriesInstallation temporaire Mode d’installationEnvironnement d’exploitation Installation permanente Connexion à la charge Conseils d’utilisationProblèmes audiovisuels communs Problème SolutionDépannage Guide de protection contre les défaillances et de dépannageRéenclenchement des circuits de l’appareil Remplacement de fusibleAccessoires RangementLa liberté de la Puissance Programme DE Garantie Restreinte DE Deux ANSCordless,MAXXRechargeableSST Normas DE SEGURIDAD/DEFINICIONES No conecte al cableado de distribución de CA Instrucciones Importantes Sobre SeguridadAdvertencia Para Reducir EL Riesgo DE Descarga Eléctrica Advertencia Para Reducir EL Riesgo DE IncendioCaracterísticas Conserve Estas InstruccionesIntroducción Controles y funcionesLa forma de onda de salida del conversor eléctrico Características de Maxx SSTPrincipio DE Operación Comparación de onda senoidal modificada y onda senoidalConsumo DE Energía DE LOS Artefactos ATENCIÓN. Para Reducir EL Riesgo DE Daños a LA PropiedadRequisitos de la fuente de energía Cuadro DEL Consumo EN Amperios Y Vatios DE ArtefactosInstrucciones DE Operación ArtefactoCómo determinar el tamaño de la batería Tiempo de funcionamientoInstalación Características de protecciónTiempos de funcionamiento de la batería Procedimientos de instalación Entorno de operaciónInstalación temporaria Diagrama de configuración de baterías permanentes Instalación permanenteSugerencias de operación Conexión a la cargaNota sobre el uso del control remoto se vende por separado Guía de protección de fallas y detección de problemas Detección DE ProblemasProblemas visuales/de audio frecuentes Problema SoluciónReemplazo de fusibles Reinicio de la unidadAlmacenamiento Mantenimiento preventivoLa libertad de la Energía Cat No. VEC054D Form No MAR
Related manuals
Manual 2 pages 33.99 Kb Manual 44 pages 27.11 Kb