AMX NXC-M/ME/MPE Baud Rate Settings, Program Port DIP switch - Program Run Disable PRD mode

Page 9
Baud Rate Settings

Product Information - NetLinx Modules

Baud Rate Settings

Baud Rate

Position 5

Position 6

Position 7

Position 8

 

 

 

 

 

9600 bps

OFF

ON

OFF

ON

 

 

 

 

 

38,400 bps (default)

OFF

ON

ON

ON

 

 

 

 

 

57,600 bps

ON

OFF

OFF

OFF

 

 

 

 

 

115,200 bps

ON

ON

ON

ON

 

 

 

 

 

DIP switch positions 3 and 4 are reserved for future features and should always be set to the Off (down) position.

Program Port DIP switch - Program Run Disable (PRD) mode

You can also use the Program Port DIP switch to set the Master Card to Program Run Disable (PRD) mode according to the settings listed in the table below:

PRD Mode Settings

PRD Mode

Position 1

Position 2

 

 

 

Normal mode (default)

OFF

OFF

PRD Mode

ON

OFF

PRD mode prevents the NetLinx program stored in the Master Card from running when you power up the Master Card. PRD mode should only be used when you suspect the resident NetLinx program is causing inadvertent communication and/or control problems. If necessary, place the Master Card in PRD mode and use the NetLinx Studio program to resolve the communication and/ or control problems with the resident NetLinx program. Then, download the new NetLinx program and try again.

Setting the Program Port DIP Switch

1.Disconnect the power supply from the 2-pin PWR (green) connector on the Master Card.

2.Remove the front faceplate and mounting screws (four) from the Master Card's front panel. Then, locate the Program Port DIP switch (to the left of the Program port).

3.Set DIP switch positions according to the information listed in the Baud Rate Settings and PRD Mode Settings tables above.

4.Replace the front panel and faceplate back onto the Master Card and reconnect the 12 VDC power supply to the 2-pin PWR connector.

NetLinx Master Cards and Modules

3

 

 

 

 

Image 9
Contents instruction manual NetLinx Master Cards and ModulesNXM-MHS, NXC-M/ME/MPE NetLinx Central Controllers and CardsAMX Limited Warranty and Disclaimer Installation and Wiring Table of ContentsProduct Information - NetLinx Modules NXC-M Master CardNetLinx Security ProgrammingProgram Port Commands NetLinx Security FeaturesSetup Security Default Security ConfigurationMain Security Menu Logging Into a SessionNetLinx Master Cards and Modules NXM-MHS NXM Modules Product Information - NetLinx ModulesNXM-MHS specifications NXM-MHS SpecificationsProgram Port DIP switch - baud rate settings NXM-MHS Specifications ContProgram Port DIP switch - Program Run Disable PRD mode Baud Rate SettingsPRD Mode Settings Setting the Program Port DIP SwitchDB-9 Program Port, Pinouts, and Signals Program Port Connections/Wiring5-Pin Program Port Pinouts and Signals DB-9 Program port front panelModes and LED Blink Patterns Modes and front panel LED blink patternsRear panel LEDs ICSNet/ICSHub Rear panel LEDs AXLinkRear panel LEDs Ethernet ME and MPE only NXC-M Master Card SpecificationsNXC-M Master Card Specifications NXC-M Master CardRear panel components Installing an optional NCP-E Ethernet Card3. Mount the NCP-E to the NXC-M, as shown in FIG NetLinx Master Cards and Modules NXC-ME Master-Ethernet Card NXC-ME SpecificationsNXC-ME Master-Ethernet Card Ethernet Ports used by the ME Ethernet Ports used by the MEPort Type Standard Port #NXC-MPE Master Port Expander Card NXC-MPE SpecificationsNXC-MPE Master Port Expander Card Ethernet 10/100 LEDs Ethernet 10/100 connector SPE Port Connection/WiringICSNet connectors/LEDs ICSHub In/Out connectors/LEDs FIG. 9 NXC-MPE Card shown mounted in a NXS-MHS Module - rear viewSPE Cable pinout information SPE Connector Pinouts and SignalsNetLinx Master Cards and Modules Installation and Wiring Mounting the Modules Into an Equipment RackMounting the Master Cards in an NXF CardFrame or NXI ICSNet RJ-45 Connections/Wiring Preparing/connecting captive wiresICSNet RJ-45 Pinouts/Signals Ethernet 10/100 Base-T RJ-45 Connections/Wiring ICSHub RJ-45 Connections/WiringISCHub Pinouts and Signals Ethernet RJ-45 Pinouts and SignalsReplacing the Lithium Batteries Programming Program Port CommandsPC COM Port Communication Settings Program Port CommandsProgram Port Commands Cont SET TIME Notes on specific Telnet/Terminal clients ESC Pass CodesESC Pass Codes Windows client programsNetLinx Security NetLinx Security FeaturesSecurity Terms Used in This Document NetLinx Security FeaturesAccess Rights PasswordUser Name Group NameInitial Setup via Telnet or Terminal connection Accessing the Security configuration optionsGetting connected If NetLinx master security is not enabled, you will see the following Security Options Menu 2 Display system security options for NetLinx master3 Add user Edit User Menu 4 Edit UserAccess Rights Menu Access Rights MenuEdit User Menu 5 Delete user Access Rights Menu Cont6 Show the list of authorized users 7 Add GroupEdit Group menu Delete directory association Edit Group Menu Add directory associationEdit Group menu Display Access Rights Edit Group menu Change Access RightsEdit Group menu List directory associations 8 Edit Group12 Display Telnet Timeout in seconds 11 Set Telnet Timeout in seconds9 Delete Group 10 Show List of Authorized GroupsMain Security Menu Main Security MenuMain Security Menu Cont Default Security ConfigurationSecurity Help Menu Options Security Help menuSecurity Help Menu Options Cont Logging Into a SessionLogout Setup SecurityHelp Security NetLinx Master Cards and Modules Panja Inc to alter specificationsAMX logo AMX reserves